beautypg.com

List of aux functions, Adjustable aux output functions – Outback Power Systems GVFX Series Inverter/Charger Programing Manual User Manual

Page 54

background image

52

LIST OF AuX FuNCTIONS

Cool Fan activates the standard TurboFan which cools the FX.
Divert DC and Divert AC allows the AUX to divert excess renewable energy to a DC or AC load,

respectively. This allows control of energy sources such as wind turbines or hydro-generators. When
using Divert AC, the AUX output will shut off if the inverter is overloaded.

AC Drop is activated when an AC power source disconnects from an FX. An indicator, such as an

alarm, connected to the AUX warns a user that AC power is no longer available.

Vent Fan provides 0.7 amps to run a 12 VDC fan for removing hydrogen from the battery

compartment. Vent Fan can operate automatically when the VENTFAN ON voltage set point is
exceeded or it can operate intermittently by adjusting the VENTFAN OFF PERIOD.

• In Fault mode, the AUX can send an alarm signal via radio, pager, or telephone device when the FX

enters into an error condition. Fault mode can also be used to log error conditions by triggering an
event recording device.

GenAlert, through a 12 VDC relay, will tell the system to start a two-wire type generator when

the battery voltage falls below a certain set point. GenAlert can be adjusted according to the
shortfallbattery voltage, the amount of time spent at this voltage, the recharged voltage and amount
of time at this voltage before GenAlert is de-energized.

Load Shed energizes the AUX to reduce the load demand on the batteries and the inverter function,

thus acting as a load management system.

• Setting the AUX to Remote allows a message sent through the serial port on the MATE to switch the

AUX on and off.

Note: Using Advanced Generator Start (AGS) overrides any programmed AUX function.

ADV/FX/AUX-------------P00

aux output Remote

function

DOWN INC DEC PORT

From the Remote aux output function screen, press

the soft key.

ADJuSTABLE AuX OuTPuT FuNCTIONS

There are four AUX functions whose settings can be adjusted by the user:
• Diversion

• Vent Fan

• GenAlert

• Load Shed

All voltage settings are given for a 24-volt inverter.

This manual is related to the following products: