background image

37

AC Breakers Off

DC Breakers On

2. With the FXs connected to the HUB, turn only the DC breakers ON and power up the components. All AC
breakers should be OFF.

Note: Powering up the FXs can cause the red ERROR
STATUS light to blink. After 5-10 seconds, the green
INVERTER light should be bright and the ERROR and
AC IN lights dark. The FX is now producing AC output
voltage.

LED Color LED Action LED Indicates

green Solid grEEN Inverter ON
Flashing grEEN

Search mode or Slave Power

Off Inverter OFF

yellow Solid yELLOw AC Source is Connected

Flashing yELLOw

AC Input Live-waiting to

Connect to the FX

Off No AC Input Present

red Solid rED Error: Error message, dis-

plays on the mATE

Flashing rED warning: Non-critical FX

fault. The mATE can access

this information

BYPASS

OUTPUT INPUT