Stacking and assigning fx status – Outback Power Systems GVFX Series Inverter/Charger Programing Manual User Manual
Page 42
40
STACkINg AND ASSIgNINg FX STATuS
Use the MATE to establish the order or hierarchy of all the system FXs by designating each one of the
following (in order as they appear on the MATE):
• Master (series stacking or 3-phase stacking)
• Classic Slave (series stacking)
• 3p Classic B (3-phase stacking)
• 3p Classic C (3-phase stacking)
Other options will be displayed, but they are not supported on this FX model.
master
• This is the default ranking of every FX.
• One Master FX is established for every multiple FX system. It applies to one-phase, two-phase or
three-phase systems.
• Each Grid-Interactive FX can be a Master as long as each is connected to a separate battery and a
separate AC output leg (both HOT and NEUTRAL).
• If one Grid-Interactive FX is designated as the system’s only Master, it is always considered to be the
Leg 1 phase.
Classic Slave
• Classic Slave is the designation of the second FX in a two-inverter, split-phase system that produces
240 VAC.
• This FX is plugged into Port 02 of the HUB and is considered to be the L2 phase.
3p Classic B
• In 3-phase stacking, the unit which is plugged into HUB Port 02 (phase B) is designated as 3p Classic B.
3p Classic C
• In 3-phase stacking, the unit which is plugged into HUB Port 03 (phase C) is designated as 3p Classic C.