POwEr SAvE LEvELS

In grid-interactive models, the power save levels affect the selling and charging functions. The master

inverter is set at the lowes power save level, which means it always acts first. The slaves should be set

at higher levels, causing them to assist the master as necessary when selling power or charging.

ADV/FX/STACK------------P01

(ANY SCREEN IN STACK PHASE)

DOWN INC DEC PORT

ADV/FX/STACK-----------P01

power save level

0

master adjust only

DOWN INC DEC PORT

• Press the soft key once to view the power

save level master adjust only screen.

• The master setting is defaulted at 0. This should not

be changed. Press the soft key to view
the power save level slave adjust only screen. Next,
press the soft key to view the slave inverter,
P02 (and P03 if present).

ADV/FX/STACK---------P02

power save level 2
slave adjust only

DOWN INC DEC PORT

• Press the soft key to change the power save

level for the slave inverters. P02 should be set to 1. If
P03 is present, repeat these steps and set it to 2.

ADV/FX/SELL-----------P01

grid tie

USER

window

DOWN IEEE USER PORT

ADV/FX/SELL-----------P01

sell re 26.0 vdc
volts

DOWN INC DEC PORT

SELL SETTINgS

Two settings in the SELL menu are significant.

• “sell re volts” stands for the voltage level at which the

inverter/charger sells renewable energy (RE) back to
the grid. This setting is recommended to be lower
than the settings for your renewable energy source,
but high enough to maintain the battery sufficientliy.

• The grid tie window has two options displayed on
the screen, but the IEEE setting is not available for
this model of inverter. USER is the only setting that
is available.