Power save levels, Sell settings – Outback Power Systems GVFX Series Inverter/Charger Programing Manual User Manual
Page 48
46
POwEr SAvE LEvELS
In grid-interactive models, the power save levels affect the selling and charging functions. The master
inverter is set at the lowes power save level, which means it always acts first. The slaves should be set
at higher levels, causing them to assist the master as necessary when selling power or charging.
ADV/FX/STACK------------P01
(ANY SCREEN IN STACK PHASE)
DOWN INC DEC PORT
ADV/FX/STACK-----------P01
power save level
0
master adjust only
DOWN INC DEC PORT
• Press the
save level master adjust only screen.
• The master setting is defaulted at 0. This should not
be changed. Press the
the power save level slave adjust only screen. Next,
press the
P02 (and P03 if present).
ADV/FX/STACK---------P02
power save level 2
slave adjust only
DOWN INC DEC PORT
• Press the
level for the slave inverters. P02 should be set to 1. If
P03 is present, repeat these steps and set it to 2.
ADV/FX/SELL-----------P01
grid tie
USER
window
DOWN IEEE USER PORT
ADV/FX/SELL-----------P01
sell re 26.0 vdc
volts
DOWN INC DEC PORT
SELL SETTINgS
Two settings in the SELL menu are significant.
• “sell re volts” stands for the voltage level at which the
inverter/charger sells renewable energy (RE) back to
the grid. This setting is recommended to be lower
than the settings for your renewable energy source,
but high enough to maintain the battery sufficientliy.
• The grid tie window has two options displayed on
the screen, but the IEEE setting is not available for
this model of inverter. USER is the only setting that
is available.