Power supply specifications – HP ProLiant DL385 G6 Server User Manual
Page 89
Specifications 89
BTUs per hour
2285 at 100V to 120V AC
input
2217 at 200V to 240V AC
input
Power supply output
Rated steady-state power
For more information, see
“Power supply specifications (on
page
Rated peak power
For more information, see
“Power supply specifications (on
page
*The system input requirements are based on measurements using hardware available at the publication
of this document. For u
Power supply specifications
The following specifications provide information on the parameters of the power supplies as they were
designed. For more information on configuring power for a specific server, see the HP website
Depending on installed options, the server is configured with one of the following power supplies:
•
HP ProLiant 460 W Power Supply
Specification Value
Input requirements
Rated input voltage
100V to 120V AC
200V to 240V AC
Rated input frequency
50Hz to 60Hz
Rated input current
5.5A at 100V AC
2.6A at 200V AC
Rated input power
526 W at 100V AC input
505 W at 200V AC input
BTUs per hour
1794 at 100V AC input
1725 at 200V AC input
Power supply output
Rated steady-state power
460 W at 100V to 120V AC
input
460 W at 200V to 240V AC
input
Rated peak power
460 W at 100V to 120V AC
input
460 W at 200V to 240V AC
input