HP Modular Cooling System User Manual
Page 52
Operator display 52
Indicators
Meaning
Condition
The water level has exceeded the permissible level of the condensation
pump sensor.
Modules or sensors
Condensation pump sensor
SNMP notification
Warning
Type of message
Warning
Solution:
1.
To determine the cause, look for leaks or condensation.
2.
If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Cycles
Warning Threshold field.
IMPORTANT:
Use caution when entering temperatures in the Condensation Pump Threshold
fields. Be sure to determine the proper default settings to prevent false alarms, without masking
problems with the MCS.
Default settings will vary, depending on the humidity level of your data center and the heat load
generated by the equipment in the MCS.
The condensation pump has run more than x seconds
Indicators
Meaning
Operator display alarm
message
Excessive moisture
Web interface alarm
message
The condensation pump has run more than x seconds
Condition
The water level has exceeded the permissible level of the condensation pump sensor.
Modules or sensors
Condensation pump sensor
SNMP notification
Warning
Type of message
Warning
Solution:
1.
To determine the cause, look for leaks or condensation.
2.
If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Running
Time Warning Threshold field.
IMPORTANT:
Use caution when entering temperatures in the Condensation Pump Threshold
fields. Be sure to determine the proper default settings to prevent false alarms, without masking
problems with the MCS.
Default settings will vary, depending on the humidity level of your data center and the heat load
generated by the equipment in the MCS.
NOTE:
A 24-hour clock starts when the condensation pump runs for the first time in more than 24
hours. A warning is issued if either the cycle threshold or pump running time is exceeded within
the 24-hour window. The clock stops and the counters are reset to zero for warning purposes if the
thresholds are not exceeded within 24 hours after the last time the condensation pump runs.