Operator display 46

Indicators

Meaning

Type of message

Warning

Solution:

1.

Remove the fan unit.

2.

Reinstall the same fan unit.

If the warning message does not clear after the module is reseated, replace the fan unit with a CSR part. For
more information on CSR parts, see "Replaceable parts and maintenance and service information (on page

59

)."

HEX (heat exchanger unit) temperature in failed (Server Intake Temperature failed)

Indicators

Meaning

Operator display alarm message HEX1, HEX2, or HEX3 Temp. In Failed

Web interface alarm message

Top Heat Exchanger Intake Air Temperature Sensor to Server Failed

Condition

Temperature reading is beyond limit (possible open circuit)

Sensors

HEX1, HEX2, or HEX3 sensors (This value is the water to air heat exchanger
unit temperature of the intake to the servers.)

SNMP notification

Warning

Type of message

Warning

Solution:
Contact HP, or see the HP website (

http://www.hp.com

).

HEX temperature out failed (Server Exhaust Temperature failed)

Indicators

Meaning

Operator display alarm message HEX1, HEX2, or HEX3 Temp. Out Failed

Web interface alarm message

Top Heat Exchanger Exhaust Air Temperature Sensor from Server Failed

Condition

The temperature reading is beyond limit (possible open circuit)

Sensors

Fan 1, 2, 3, 4, 5 or 6 sensors (This value is the fan unit temperature of the

exhaust from the servers.)

SNMP notification

Warning

Type of message

Warning

Solution:
Contact HP, or see the HP website (

http://www.hp.com

).

Low water flow

Indicators

Meaning

Operator display alarm message Water flow Low
Web interface alarm message

Water flow Low

Condition

No or low water flow

Modules

Water group

SNMP notification

Warning

Type of message

Warning