beautypg.com

HP Modular Cooling System User Manual

Page 49

background image

Operator display 49

Indicators

Meaning

Operator display alarm message Temperature too high

Web interface alarm message

Temperature too high

Condition

Heat overload condition

Modules or sensors

The average server air temperature is above the temperature assigned in the
web interface Intake Temp tab High Temperature Threshold field.

SNMP notification

Critical

Type of message

Alarm

Solution:

1.

Verify the water inlet temperature.

2.

Verify that the flow matches the specifications required for heat load.

3.

Adjust the temperature assigned in the web interface Intake Temp tab High Temperature Threshold field.

Leakage detected

Indicators

Meaning

Operator display alarm message Leakage Detected

Web interface alarm message

Leakage Detected

Condition

Leak is detected

Modules or sensors

Leakage detector actuated

SNMP notification

Critical

Type of message

Alarm

Solution:

1.

Open the rack doors.

2.

Power down the rack-mounted components.

3.

Turn off the water to the MCS-200 unit.

4.

Locate and correct the leak.

Communication failure

Indicators

Meaning

Operator display alarm message Comm. Failure I²C

Web interface alarm message

Comm. Failure I²C

Condition

The management module cannot communicate with the MCS-200 unit

sensors.

Modules or sensors

Any module or sensor

SNMP notification

Critical

Type of message

Alarm

Solution:
Power cycle the management module. If the alarm message continues to appear, replace the management

module with a CSR part. For more information on CSR parts, see "Replaceable parts and maintenance and

service information (on page

59

)."