Operator display, Operator display overview, Operator display components – HP Modular Cooling System User Manual
Page 45: Warning and alarm messages
Operator display 45
Operator display
Operator display overview
The operator display provides information on the system operation, viewable on the outside of the MCS-200
front door. When the management module issues an alarm or warning, the warning and alarm messages
display ("
" on page
) on the operator display, as well as on the web
interface Alarms menu and Alarm History menu.
Operator display components
The operator display on the front door of the MCS-200 unit has a digital touch-screen.
To scroll through the menu options, press the appropriate button on the bottom of the screen.
Warning and alarm messages
The following tables describe the possible warning and alarm messages that the MCS-200 unit sends to the
management module. These messages appear on the operator display and on the web interface Alarms
menu and Alarm History menu.
Fan unit failed or not installed
Indicators
Meaning
Operator display alarm message Fan 1, 2, 3, 4, 5, or 6 Failed
Web interface alarm message
Fan 1, 2, 3, 4, 5, or 6 Failed or Not Installed
Condition
Fan 1, 2, 3, 4, 5, or 6 is running at less than the minimum RPM
Sensors
Fan 1, 2, 3, 4, 5, or 6
SNMP notification
Warning