Configuring the ups – HP Tower Uninterruptible Power System User Manual
Page 42

UPS operations 42
NOTE:
If the On and Off buttons are simultaneously pressed, the Off button has priority over the
On button.
Button
Assertion
time
Audible alarm Mode before
assertion
Utility
present ?
Action
On
0.5 seconds Every 0.5 seconds
until the button is
released
Standby
Yes
Energizes the load and
resets the bypass entry count
to 0
Operate
Yes
Resets the bypass entry count
to 0
Auto-Bypass
Yes
Clears the UPS On audible
alarms, resets the bypass
entry count to 0, and
attempts to transfer to
Operate mode
Converter Off
Yes
Clears the UPS On audible
alarms, resets the bypass
entry count to 0, and
attempts to transfer to
Operate mode
Off
3 seconds
Every 0.5 seconds
until the button is
released
Operate
Yes
Transfers to Standby mode,
and power to the load
ceases
Standby
Yes
No action
Battery
No
Powers down the UPS, and
power to the load ceases
Auto-bypass
Yes or No
Transfers to Standby mode
or Converter Off mode, and
power to the load ceases
Self Test
0.5 seconds
Any
Yes or No
Silences audible alarms after
0.5 seconds
3 seconds
Continuously
Any
Yes or No
Initiates a self-test
Battery Start 0.5 seconds
Any
Yes or No
No action
Battery Start
and On
3 seconds
Continuously
UPS off
No
Transfers to battery power,
and begins powering the
load
On and Self
Test
3 seconds
Continuously
Any
Yes or No
Enters or exits Configuration
mode
Configuring the UPS
The UPS automatically detects the number of ERMs connected.
In Configure mode, the LED front panel display changes function to enable modification of the UPS
parameters. Each LED is associated with a different parameter.
Available settings
Parameter
Associated LED
Explanation (when LED is illuminated)
Nominal voltage
setting
100/204 Nom Self Test
Nominal output voltage is 100 V for a low
voltage model and 204 V for a high voltage
model