beautypg.com

Connecting the ground bonding cable – HP Tower Uninterruptible Power System User Manual

Page 23

background image

Installation 23

Avoid allowing the wires to hang in the rear of the UPS.

Use tie wraps and tie wrap blocks to secure the wires tightly to the rack and the rear of the UPS.

For more information about the REPO port, see "REPO port (on page

11

)".

For information about verifying the REPO connection, see "Verifying the REPO port connection (on page

44

)".

Connecting the ground bonding cable

NOTE:

UPS appearance might vary depending on the specific unit installed.

The ground bonding screw is provided as an attachment point for conductors. Use a ground bonding cable
if the rack contains any conductors for the purpose of functional grounding or bonding of ungrounded metal

parts.