Population order, Installing a dimm, Hot-plug hard drive guidelines – HP ProLiant SL4540 Gen8 Server User Manual
Page 38
![background image](/manuals/398082/38/background.png)
Hardware options installation 38
Population order
For memory configurations with a single processor or multiple processors, populate the DIMM slots
sequentially in alphabetical order (A through F).
After installing the DIMMs, use RBSU to configure memory support.
Installing a DIMM
CAUTION:
To avoid damage to the hard drives, memory, and other system components, the air
baffle, drive blanks, and access panel must be installed when the server is powered up.
1.
2.
Remove the node from the chassis ("
Remove a node from the chassis
" on page
3.
Remove the access panel (on page
4.
Open the DIMM slot latches.
5.
Install the DIMM.
6.
Install the access panel (on page
7.
Install the node into the chassis ("
Installing a node into the chassis
" on page
8.
Power up the node ("
Powering up and configuring the server
" on page
To configure the memory mode, use RBSU ("
" on page
Hot-plug hard drive guidelines
When adding hard drives to the node, observe the following general guidelines:
•
The system automatically sets all device numbers.
•
If only one hard drive is used, install it in the bay with the lowest bay number.
•
Drives should be the same capacity to provide the greatest storage space efficiency when drives are
grouped together into the same drive array.