Troubleshooting, Led and audible alarm troubleshooting – HP UPS Extended Runtime Module User Manual
Page 41
Troubleshooting 41
Troubleshooting
LED and audible alarm troubleshooting
Genera
l Alarm
LED
On
Batter
y LED
Batter
y Fault
LED
Site
Wiring
Fault
LED
Utility
LED
Overloa
d LED
Audible
alarm
Can
alarm be
silenced
("
on page
Condition
Off
Off
Off
Off
Green
Off
No audible
alarm
N/A
UPS is in Operate
mode (on page
Off
Off
Off
Off
Flashin
g
green
Off
No audible
alarm
N/A
UPS is in Standby
mode (on page
Off
Off
Off
Off
Red
Off
On—1 beep
every 5
seconds
Yes
UPS is in Auto-Bypass
mode (on page
Flashing
red
Off
Off
Off
Red
Off
On—1 beep
every 5
seconds
Yes
General alarm
condition—UPS is in
Auto-Bypass mode
("
" on page
Off
Off
Off
Off
Flashin
g red
Off
On—1 beep
every 5
seconds
Yes
Bypass is out of range
(on page
Off
Off
Flashin
g red
Off
Off
Off
On—1 beep
every 5
seconds
Yes
Battery test failure
("
Off
Flashin
g red
Off
Off
Off
Off
On—1 beep
every 5
seconds
No
Low battery (no utility
power) ("
" on page
Off
Off
Flashin
g red
Off
Off
Off
On—1 beep
every 5
seconds
Yes
Batteries are
disconnected ("
" on page
Off
Red
Off
Off
Off
Off
On—1 beep
every 5
seconds
Yes
On battery—No utility
power ("
" on page