beautypg.com

Troubleshooting, Led and audible alarm troubleshooting – HP UPS Extended Runtime Module User Manual

Page 41

background image

Troubleshooting 41

Troubleshooting

LED and audible alarm troubleshooting

Genera
l Alarm
LED

On
Batter
y LED

Batter
y Fault
LED

Site
Wiring
Fault
LED

Utility
LED

Overloa
d LED

Audible
alarm

Can
alarm be
silenced
("

Silencin

g an
audible
alarm

"

on page

31

)?

Condition

Off

Off

Off

Off

Green

Off

No audible
alarm

N/A

UPS is in Operate
mode (on page

27

)

Off

Off

Off

Off

Flashin
g
green

Off

No audible
alarm

N/A

UPS is in Standby
mode (on page

27

)

Off

Off

Off

Off

Red

Off

On—1 beep
every 5
seconds

Yes

UPS is in Auto-Bypass
mode (on page

28

)

Flashing
red

Off

Off

Off

Red

Off

On—1 beep
every 5
seconds

Yes

General alarm
condition—UPS is in
Auto-Bypass mode
("

General alarm

condition

" on page

42

)

Off

Off

Off

Off

Flashin
g red

Off

On—1 beep
every 5
seconds

Yes

Bypass is out of range
(on page

43

)

Off

Off

Flashin
g red

Off

Off

Off

On—1 beep
every 5
seconds

Yes

Battery test failure
("

Battery condition

"

on page

43

)

Off

Flashin
g red

Off

Off

Off

Off

On—1 beep
every 5
seconds

No

Low battery (no utility
power) ("

UPS is on

battery

" on page

43

)

Off

Off

Flashin
g red

Off

Off

Off

On—1 beep
every 5
seconds

Yes

Batteries are
disconnected ("

Battery

condition

" on page

43

)

Off

Red

Off

Off

Off

Off

On—1 beep
every 5
seconds

Yes

On battery—No utility
power ("

UPS is on

battery

" on page

43

)