Available voltage settings, Initiating a self-test – HP UPS Extended Runtime Module User Manual
Page 30

UPS operations 30
NOTE:
Configure mode times out after 2 minutes of inactivity. If the Test/Alarm Reset button
has not been pressed, any new selections are not saved.
For the location of buttons, see "UPS front panel controls (on page
)."
For the location of LEDs, see "UPS front panel LED indicators (on page
)."
Available voltage settings
NOTE:
An asterisk (*) indicates the default setting.
UPS model
Available settings utility voltage (VAC)
Associated LED ("
" on page
R3000 NA
100
General Alarm
110
On Battery
120*
Battery Fault
127
Site Wiring Fault
R3000j JPN
100*
General Alarm
110
On Battery
120
Battery Fault
127
Site Wiring Fault
R3000h NA, R3000h JPN
200/208*
General Alarm
220
On Battery
230
Battery Fault
240
Site Wiring Fault
R3000 INT
200/208
General Alarm
220
On Battery
230*
Battery Fault
240
Site Wiring Fault
Initiating a self-test
To initiate a self-test, press and hold the Test/Alarm Reset button ("
" on page
for three seconds.
Because a portion of the self-test requires battery power, the self-test cannot be initiated if the batteries are
less than 90 percent charged. If the UPS detects a problem, the appropriate LED ("
" on page
) illuminates and an audible alarm may sound.
For information on what to do if the self-test detects a problem, see "Troubleshooting (on page
)."