7.9.12 Examples of communications to be written
Example: Request message: Requests that the temperature alarm output setting of EIF in channel 1
(High-level computer)
of unit number 3 be changed to deviation top/bottom alarm + holding.
In response to that,
Response message: This returns a notice that the request message has been received.
(This product)
*Check that it has been correctly written by reading the data separately.
Write request message (transmitted from a high-level computer)
S
T
X
3 1 W E 1 F 0 0 0 1 1
E
T
X
B
C
C
① ② ③ ④
―⑤―
―――⑥―――
⑦ ⑧
Response message (returned from this product)
S
T
X
3 1
A
C
K
E
T
X
B
C
C
① ② ③ ⑨ ⑦ ⑧
Code
Code, data
ASCII code, note 2)
① Start code
STX
02H
② Unit number
3
33H
③ Channel number
1
31H
④ Request contents
W (Write)
57H
⑤ Identifier, note 1)
E1F
41H 34H 46H
⑥ Numerical data
00011
30H 30H 30H 31H 31H
⑦ End code
ETX
03H
⑧ BCC data request
56H
response
05H
⑨ Acknowledge code
ACK
06H
Note 1): See "6. Table of identifiers (codes)."