10 parameter – TOHO ELECTRONICS TTM-00BT User Manual
Page 10
10
Parameter
a) Identifier
b) Name
c) R/W
d) Description and set range
e) Remark
Initial value (communication
numerical data)
TC, thermocouple;
Pt, resistance bulb
SV1
00000
Setting
R/W
r/w
R/W of the control settings
Thermocouple input:
Thermocouple K, 0.0 to 1300.0
°
C
Thermocouple J, 0.0 to 800.0
°
C
Resistance bulb input: PT100/JPT, -199.9 to 500.0
°
C
□CF
00000
Set a temperature unit
R/W
R/W of the
°
C/
°
F
°
C: 00000
°
F: 00001
Channel not specified
INP
TC: 00000
Pt: 00010
Set an input type
R/W
R/W of the input type settings
Thermocouple input models:
Thermocouple K: 00000
Thermocouple J: 00001
Resistance bulb input models:
Pt100: 00010
JPt: 00011
Neither the
thermocouple input nor
the resistance bulb
input can be changed.
PVG
00100
Set a PV correction gain
R/W
r/w
R/W of the PV correction gain setting
Set range: 0.50 to 2.00 times
Measurement
Gain correction
PVS
00000
Set a PV correction zero
point
R/W
r/w
R/W of the PV correction zero setting
Set range: -199 to 999
°
C/-199.9 to 999.9
°
C
Measurement
Zero correction
00001
Set an input filter
R/W
R/W of the input filter setting
Set range: 0 to 99 seconds
□DP
TC: 00000
Pt: 00001
Set a decimal point
R/W
R/W of the decimal point setting
No decimal point: 00000
Decimal point provided: 00001
□AT
00000
Start/release AT
R/W
R/W of the AT start/release
Start: 00001
Release: 00000
The W is not possible
during ON/OFF
control.