15 control parameters – TOHO ELECTRONICS TTM-00BT User Manual
Page 15
15
Control parameters
a) Identifier
b) Name
c) R/W
d) Description and set range
e) Remark
Initial value (communication
numerical data)
TC, thermocouple;
Pt, resistance bulb
MH1
01000
Set an operation quantity
limiter, top limit
R/W
r/w
R/W of the operation quantity limiter, top limit setting
Set range: Operation quantity limiter, bottom limit
setting to 100.0%
ML1
00000
Set an operation quantity
limiter, bottom limit
R/W
r/w
R/W of the operation limiter, bottom limit setting
Set range: 0.0 to operation quantity limiter, top limit
setting
□C1
00000
Set a control output 1,
control sensitivity
R/W
r/w
R/W of the control output 1, control sensitivity setting
Set range: 0 to 999
°
C/0.0 to 999.9
°
C
CP1
00000
Control output 1
Set an OFF point
R/W
r/w
R/W of the OFF point setting of control output 1
Set range: -199 to 999
°
C/-199.9 to 999.9
°
C
MV2
00000
Control output 2 operation
quantity
R/W
r/w
R/W of the control output 2 operation quantity
Display range: 0.0 to 100.0%
Set range: ML1 to MH1
□P2
00020
Set control output 2,
proportional band
R/W
r/w
R/W of the control output 2, proportional band setting
Set range: 0.10 to 10.00 times
(Magnification for output 1, proportional band)
□T2
00020
Set control output 2,
proportional period
R/W
r/w
R/W of the control output 2, proportional period
setting
Set range: 1 to 120 seconds
MH2
01000
Set an operation quantity
limiter, top limit
R/W
r/w
R/W of the operation quantity limiter, top limit setting
Set range: Operation quantity limiter, bottom limit
setting to 100.0%
ML2
00000
Set an operation quantity
limiter, bottom limit
R/W
r/w
R/W of the operation limiter, bottom limit setting
Set range: 0.0 to operation quantity limiter, top limit
setting
□C2
00000
Set a control output 2,
control sensitivity
R/W
r/w
R/W of the control output 2, control sensitivity setting
Set range: 0 to 999
°
C/0.0 to 999.9
°
C
CP2
00000
Control output 2
Set an OFF point
R/W
r/w
R/W of the OFF point setting of control output 2
Set range: -199 to 999
°
C/-199.9 to 999.9
°
C
PBB
00000
Manual reset
R/W
r/w
R/W of the manual reset
Set range: 0.0 to 100.0%
But -100.0 to +100.0% during heating/cooling control
□DB
00000
Set a dead band
R/W
r/w
R/W of the dead band
Set range: -100 to 100
°
C/-100.0 to 100.0
°
C
STR
Save data
W
Save data
*1: If the control output 2 control type is ON/OFF control or PID control (if heating/cooling control is conducted), this product cannot be
used as a temperature alarm output.
*2: If the control output 2 control type is used as a temperature alarm output, the monitor for the control output of control output 2 is fixed at
0.
*3: If the control output 2 control type is used as ON/OFF control or as PID control, the temperature alarm output monitor is fixed at 0.
*4: If the control output 2 control type is set to "None": This product produces a temperature alarm output.
For ON/OFF control or PID control: This product performs heating/cooling control.