11 event output parameters – TOHO ELECTRONICS TTM-00BT User Manual
Page 11
11
Event output parameters
a) Identifier
b) Name
c) R/W
d) Description and set range
e) Remark
Initial value (communication
numerical data)
TC, thermocouple;
Pt, resistance bulb
E * F
*: 1 to 8
00000
Temperature alarm
output*functional setting
R/W
R/W of the temperature alarm output*functional
setting
000 * *
PV temperature alarm functions
Type
0 None
1 Deviation top/bottom limit alarm
Additional functions
2 Deviation top limit alarm
Type
3 Deviation bottom limit alarm
0 None
4 Deviation range alarm
1 Hold
5 Absolute value top/bottom limit
alarm
2 Standby sequence
6 Absolute value top limit alarm
3 Hold + standby
sequence
7 Absolute value bottom limit
alarm
8 Absolute value range alarm
*1
E * H
*: 1 to 8
00000
Set a temperature alarm
output*top limit
R/W
r/w
R/W of the temperature alarm output*top limit setting
Set range: -199 to1500
°
C/-199.9 to 1500.0
°
C
*1
E * L
*: 1 to 8
00000
Set a temperature alarm
output*bottom limit
R/W
r/w
R/W of the temperature alarm output*bottom limit
setting
Set range: -199 to1500
°
C/-199.9 to 1500.0
°
C
*1
E * C
*: 1 to 8
00000
Set a temperature alarm
output*sensitivity
R/W
R/W of the temperature alarm output*sensitivity
setting
Set range: -199 to1500
°
C/-199.9 to 1500.0
°
C
*1
CTF
00000
CT function
R/W
R/W of the presence or lack of an alarm about heater
wire break and SSR breakdown
00000: None
00001: Heater wire break alarm function
00002: SSR breakdown alarm function
00003: Heater wire break + SSR breakdown alarm
function
Heater wire break:
LED12
SSR breakdown:
LED13
C * I
*: 1 to 8
00000
CT allocation channel
R/W
R/W of the status about the channel to which CT*(1 to
8) should be allocated
00000: None (not allocated)
00001 to 00008: (CH)
Channel not specified
ALB
00000
Error alarm function
R/W
R/W of the presence or lack of memory errors, A/D
errors, and sensor error alarms
00000: None
00001: Present
Error alarm: LED14
CT*
*: 1 to 8
00000
Set an output current error
R/W
R/W of the current of the heater current detector
Set range: 0.0 to 50.0A AC
Channel not specified