13 monitor window parameters – TOHO ELECTRONICS TTM-00BT User Manual
Page 13

13
Monitor window parameters
a) Identifier
b) Name
c) R/W
d) Description and set range
e) Remark
 
 
PV1
Measurement
R
Used as a measurement monitor 
When over-scale: HHHHH (the same is true when the 
sensor has a wire break) 
When under-scale: LLLLL 
CM*
*: 1 to 8
CT measurement
R
R of the measured current of the heater current 
detector 
When over-scale: HHHHH 
When reading is impossible: ----- 
When reading is 
impossible: The CT 
value cannot be read 
unless the output of no 
less than 190mS is 
turned on. 
DIM
DI monitor
R
R of the voltage input monitoring 
00000: State where voltage input is not applied 
00001: State where voltage input is applied 
OM1
Monitor the control output
R
R of the control output monitoring 
000①② 
① Output 1 state… 1:ON/0:OFF 
② Output 2 state… 1:ON/0:OFF 
*2
EM1
Monitor the temperature 
alarm outputs 1 to 4 
R
R of the temperature alarm output monitoring 
0①②③④ 
①: temperature alarm output 4 
②: temperature alarm output 3 
③: temperature alarm output 2 
④: temperature alarm output 1
*3
EM2
Monitor the temperature 
alarm outputs 5 to 8 
R
R of the temperature alarm output monitoring 
0①②③④ 
①: temperature alarm output 8
②: temperature alarm output 7 
③: temperature alarm output 6 
④: temperature alarm output 5
*3
ALM
Monitor the alarm output
R
R of the alarm monitoring 
00①②③ 
① Alarm output of heater wire break (1:ON/0:OFF) 
② Alarm output of SSR breakdown (1:ON/0:OFF) 
③ Error alarm output (1:ON/0:OFF)