7.5 Temperature alarm output
7.5.1 Temperature alarm output: Compare the measurements with the setting value of the
temperature alarm output and turn on and off the temperature alarm output.
 
• Operation table of temperature alarm outputs 
1. Deviation top/bottom limit
5. Absolute value top/bottom limit
E*C
SV
E*C
E*L
E*H
△
0℃( v
)
E*C
E*C
E*L
E*H
2. Deviation top limit
6. Absolute value top limit
SV
E*C
E*H
△
0℃( v
)
E*C
E*H
3. Deviation bottom/limit
7. Absolute value bottom limit
E*C
SV
E*L
△
0℃( v
)
E*C
E*L
4. Deviation top/bottom limit range
8. Absolute value top/bottom limit range
E*C
SV
E*L
E*H
△
E*C
E*C
E*C
0℃( v
)
E*L
E*H
Operation range of temperature alarm output: E*L, bottom limit setting of temperature alarm output; E*H, top 
limit setting of temperature alarm output; E*C, temperature alarm sensitivity 
 
 
7.5.2 Additional functions
• Standby sequence 
 This function inhibits temperature alarm output even if the conditions are met for temperature 
alarm output when this product is turned on. Temperature alarm output is generated only when 
this product deviates from the conditions for temperature alarm output and satisfies those 
conditions again. This function is used for bottom temperature alarm output when this product 
is turned on. This function is enabled when this product is turned on in the shaded portion in 
the operation table of temperature alarm outputs. 
 [How to cancel this function] 
 This function is canceled when this product is activated or when either of the following setting is 
changed: target, temperature alarm, PV correction, and temperature alarm setting.
• Temperature alarm output holding 
 When a temperature alarm output is generated, this function retains that state. Even if this 
product deviates from the conditions for temperature alarm output, the temperature alarm output 
will remain on. 
 [How to cancel this function] 
 To cancel this function, turn this product off and back on or disable the additional function for 
temperature alarm output setting.