Function description, 1 display range and set range of temperature input, 3 voltage input – TOHO ELECTRONICS TTM-00BT User Manual
Page 16: 4 control output
16
7. Function description
7.1 Display range and set range of temperature input
7.1.1 Display range and set range of thermocouple input (JIS C 1602 - 1995)
Set range with a
decimal point
Display range with a
decimal point
Set range without a
decimal point
Display range without
a decimal point
K (JIS)
0.0 to 1300.0
°
C
-40.0 to 1326.0
°
C
0 to 1300
°
C
-40 to 1326
°
C
J (JIS)
0.0 to 800.0
°
C
-31.0 to 850.0
°
C
0 to 800
°
C
-31 to 850
°
C
7.1.2 Display range and set range of resistance bulb input (JIS C 1604 - 1997)
Set range with a
decimal point
Display range with a
decimal point
Set range without a
decimal point
Display range without
a decimal point
Pt100 (JIS)
JPt100 (JIS)
-199.9 to 500.0
°
C
-199.9 to 539.1
°
C
-199 to 500
°
C
-199 to 539
°
C
7.2 Display range and set range of current detector input
7.2.1 Display range and set range: 0.0 to 50.0A AC
7.3 Voltage input
7.3.1 Voltage input: Entering a voltage (12 to 24V DC) from outside enables the selection of
functions from "7.3.2. Voltage input functions."
7.3.2 Voltage input functions
Function type
When voltage is applied
None
SV/SV2 function
SV2
RUN/READY function
READY
Auto/manual function
Manual
Forward/reverse operation function
Forward operation
Auto-tuning function
AT start
Forward operation (SV2)/reverse operation (SV) function
Forward operation (SV2)
7.4 Control output
Control output is ensured by open collector output. Control operations can be selected from
heating control or heating/cooling control (types A and B). Setting the output 2 control type to
"ON/OFF control" or "PID control" activates heating/cooling control.
Note that heating/cooling control is fixed at control output on the side of heating output, and at
temperature alarm output on the side of cooling output. See the table below for the allocation of
control outputs and temperature alarm outputs for heating control and heating/cooling control.
Heating control
Heating/cooling control
Input
Control output
Temperature alarm
output
Control output
Cooling output (temperature alarm output
is used as cooling output)
1CH
2CH
3CH
4CH
5CH
6CH
7CH
8CH
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8