5.8

Common parameter setting mode SET 10

SET10

Name

Setting content

Initial value

1

INP1 Input type setting (*2) (*3)

0 K thermocouple

11 PR40-20

0

1 J thermocouple

12 PLII

2 T thermocouple

13 Pt100

3 E thermocouple

14 JPt100

4 R thermocouple

15 0 - 10 mV DC

5 S thermocouple

16 0 - 1 V DC

6 B thermocouple

17 0 - 5 V DC

7 N thermocouple

18 1 - 5 V DC

8 U thermocouple

19 0 - 10 V DC

9 L thermocouple

20 4 - 20 mA DC

10 WRe5-26

2

FSH1 Scaling upper limit setting (*2) (*3) Current/voltage input only

FSL1 to 29999 (digit)

10000

3

FSL1 Scaling lower limit setting (*2) (*3) Current/voltage input only

-19999 to FSH1 (digit)

-10000

4

PVG1 PV compensation gain setting

0.500 to 2.000 (times)

1.000

5

PVS1 PV compensation zero setting

Thermocouple/RTD input
-999.9 to 999.9 (

C)

-999 to 999 (

C)

0

Current/voltage input
-9999 to 9999 (digit)

6

PDF1 PV filter setting

0.0 to 99.9 (seconds)

0.0

7

PDFS Special PV filter setting

0.0 to 99.9 (seconds)

0.0

8

DP1 Decimal point position

setting (*2) (*3)

Thermocouple/RTD input

0

0 Unit of 1

C

0.0 Unit of 0.1

C

Current/voltage input

0 1/digit

0.0 0.1/digit

0.00 0.01/digit

0.000 0.001/digit

0.0000 0.0001/digit

5.9

Common parameter setting mode SET 11

SET11

Name

Setting content

Initial value

1

BKUP Backup of a setting value (*2) (*3)

Backup begins by holding the  and  keys pressed for 2 seconds.
During the backup, “SAVE” is displayed; turn-off of the display indicates
ended backup.

2

RESET Initialization of a setting value (*2)

Initialization of the backup setting begins by holding both  and  keys
pressed for 2 seconds.
During initialization, “LoAd” is displayed and turn-off of the display
indicates ended initialization.