VENTING INSTRUCTIONS
WARNING: Improper venting of this appliance can result in excessive levels of 
carbon monoxide which can result in severe personal injury or death.
 
This water heater must be vented in accordance with the section “Venting of Equipment" of the 
latest edition of the Natural Fuel Gas Code: ANSI Z223.1, All applicable local building codes, 
Section 7 of CAN/CSA B149.1 Natural Gas in Canada, Propane Installation Code in Canada. 
 
EXHAUST VENT
This is a Category III appliance and must be vented accordingly. The vent system must be 
sealed air tight. All seams and joints without gaskets must be sealed with high heat resistant 
silicone sealant or UL listed aluminum adhesive tape having a minimum temperature rating of 
350ºF. For best results, a vent system should be as short and straight as possible. 
1.
This Takagi water heater is a Category III appliance and must be vented accordingly with 
any 4” vent approved for use with Category III or Special BH type gas vent. 
2.
TAKAGI recommends the “T-Vent” line manufactured by TAKAGI (Refer to Takagi’s 
“T-Vent” brochure for details). However, the following are also UL listed manufacturers: 
ProTech Systems Inc. (FasNSeal), Flex-L Inc., Z-Flex Inc. (Z-Vent III), Metal-Fab Inc., and 
Heat-Fab Inc. (Saf-T Vent). 
3.
Follow the vent pipe manufacturer’s instructions when installing the vent pipe.
4. Do not common vent this appliance with any other vented appliance (Do not
terminate vent into a chimney. If the vent must go through the chimney, the vent must run 
all the way through the chimney with Category III approved or Special BH vent pipe). 
5.
The maximum length of exhaust vent piping must not exceed 50 ft. deducting 5 ft. for each 
elbow used in the venting system. Do not use more than 5 elbows. 
Diameter
Max. No. of Elbow
Max. Vertical or Horizontal run in Length
4”
5 Ea.
50 ft
*For each elbow added, deduct 5 ft. from max. vent length.
No. of Elbows
Max. Vertical or Horizontal Length
0 50
ft.
1 45
ft.
2 40
ft.
5 25
ft.
 
6. 
When the horizontal vent run exceeds 5 ft., support the vent run at 3 ft. intervals with 
overhead hangars. 
7.
Takagi will not be responsible for any damage to the water heater caused by condensation 
from the vent. Installing a condensate drip is recommended. Please refer to p. 13 for the 
diagrams. 
When installing the vent system, all applicable national and local codes must be 
followed. If you install thimbles, fire stops or other protective devices and they 
penetrate any combustible or noncombustible construction, be sure to follow all 
applicable national and local codes.