Bring properly sized power leads and ground from a fused disconnect (installed
by your electrician) to the unit. Provide external overcurrent protection to the
unit, using circuit breakers or fuses. If you use fuses, make sure that they are
dual-element time-delay fuses, sized according to your electrical code. Make sure
that all electrical connections are tight.

Important!

1. Electrical connections must comply with all applicable electrical codes.

2. The temperature control unit must be grounded in accordance with NEC Article

250.

3. Voltage must be within plus or minus ten percent (

±10%) of the nameplate rating.

4. Make sure your installer provides external protection.