6 process water considerations, 7 making process water connections, 8 making cooling water connections – Sterlco Micro Series Water Temperature Control Unit User Manual
Page 15

MICRO Series Water Temperature Control Units
Page 15
3-6 Process Water Considerations
Raw Water
Water treatment is vital in any piping system. In some cases, raw water may be 
used in the system without problems; in other cases, it can result in large deposits 
of scale and corrosion. 
The manufacturer offers a complete line of water treatment equipment. Contact 
your manufacturer sales representative for water testing and treatment options. 
Distilled Water
Non-ferrous (brass, copper, or high-temperature plastic) piping is recommended 
for distilled water processes. 
Deionized Water
Stainless steel (316 SS minimum) or PVC plastic components must be used with deionized 
water. We recommend stainless steel because of the temperature constraints with plastic. 
3-7 Making Process Water Connections
Direct Injection
For both types of systems, the connections are basically the 
same. On the back of each unit, the connections are labeled appropriately. 
Connect the TO PROCESS hookup to the 
entrance of the process and the FROM PROCESS hookup to 
the exit of the process. Connect the PROCESS WATER 
SUPPLY to your plant water supply. Connect the COOLING WATER OUT 
line to an open drain, or to the return line of 
your central water system. 
Make sure you carefully select the connecting lines and connectors between 
the temperature control unit and the process to suit the needs and 
requirements of your application. 
If your unit has a maximum operating temperature of 250ºF (121ºC), the 
connecting lines and connectors should have a service rating of at least 250ºF 
(121ºC) and 150 psig (1,034.25 kPa/10.34 bars). 
TO PROCESS — ¾” NPT
This is the outlet for the tempered water leading to the process being controlled.
FROM PROCESS — ¾” NPT
Water from the process re-enters the MICRO Series system to be tempered and 
re-circulated back into the process. 
3-8 Making Cooling Water Connections
WATER IN — ¾” NPT
The cooling water supply inlet from a cooling tower, a chiller, or a city 
water supply. 
