Caution – Sterlco Micro Series Water Temperature Control Unit User Manual
Page 14

Page 14
MICRO Series Water Temperature Control Units
3-4 Piping
Considerations
for Permanent Installations
We recommend an optional (or customer-installed) strainer on the COOLING 
WATER IN inlet. 
The unit must have at least 16 psig (110.32 kPa/1.1 bars) water supply pressure 
to prevent pump cavitation that can be caused by the water “flashing” to steam. 
To avoid damage to the pump or other components, make sure that maximum 
supply pressure does not exceed 40 psig (275.8 kPa/2.8 bars). 
Keep restrictions to a minimum by using proper inlet pipe sizing. If the water 
supply piping is larger than ¾”, reduce the size at the unit. The table below 
contains the pipe sizes that are used in the unit. 
Pipe sizes for ½ hp and ¾ hp (0.37 kW and 0.56 kW) units
Location
Size in inches NPT
Process delivery
¾”
Process return
¾”
Water supply
¾”
Drain ¾”
Common black pipe is recommended for permanent installations. MICRO Series 
water circuit piping is non-ferrous (stainless steel and brass) and reacts electro-
chemically with ferrous metallic materials such as iron. Some water contains 
dissolved minerals that greatly accelerates the reaction between dissimilar metals. 
Non-ferrous piping is recommended to minimize galvanic action. If piping must 
be copper, use dielectric unions at the unit. 
3-5 Piping Considerations for High Mobility Installations
Mobile MICRO Series systems must use high quality hose rated for at least 150 
psig and 250
°F (1,034.25 kPa/10.34 bars and 121ºC).
Quick disconnects may be used for mobility, although they cause a drop in 
pressure. If used, they must be sized carefully to minimize pressure drop. Don’t 
use quick disconnects with check valves unless absolutely necessary. 
!
CAUTION
Non-relieving quick connect fittings or check valves on the water supply
must have a pressure relief piped to the drain.
Failure to do so could result in a dangerous over-pressure condition!
