4.2 Zero and Span Calibration
Set the Voltage Source to 0 VDC and Connect the Voltage Source to the +S
and COM terminals on the display.
Check the field sensor input and output specification.
Example:
humidity Sensor
0-100% Rh and 0 to 5 VDC output
Temperature Sensor
50-90°F and 0 to 10 VDC output
Setup humidity Sensor:
Apply 0 V and if necessary turn the ZERO potentiometer (pot) until the display
reads 0.0, apply 5 VDC and turn the pot labeled 5V until the display reads
100.0
Setup Temperature Sensor:
Move the range jumper from the 5V to 10V position. Apply 0 VDC and turn
ZERO pot until the display reads 50.0, apply 10V and turn 10V pot until display
reads 90.0
4.3 Adjust Display Brightness
While looking at the display, turn the Display brightness adjust pot, (See Fig. 4)
to the desired brightness.
- Model ASM (8 pages)
- Model 204 (4 pages)
- Model 209 (4 pages)
- Model 227 (8 pages)
- 264 (4 pages)
- 269 (4 pages)
- Model 280E (4 pages)
- Model 370 (48 pages)
- Model 526 (7 pages)
- Model 540 (9 pages)
- Model 595 (8 pages)
- Model 869 (28 pages)
- Model 321 (4 pages)
- Model SRH (12 pages)
- Model Datum 2000 (31 pages)
- Model 217 (8 pages)
- Model 230 (12 pages)
- Model 242901-06 (1 page)
- Model 265 (4 pages)
- Model 270 (5 pages)
- Model 299 (4 pages)
- Model 470 (35 pages)
- Model 524 (6 pages)
- Model 546 (8 pages)
- Model 730 (16 pages)
- GCT-225 (8 pages)
- Model 141 (4 pages)
- Model 205-2 (4 pages)
- Model 223 (8 pages)
- Model 231 (12 pages)
- Model 256 (8 pages)
- Model 276 (2 pages)
- Model 3100 (8 pages)
- Model 516 (6 pages)
- Model 550 (9 pages)
- Model 760 (18 pages)
- Model LD330 (4 pages)
- Model 201 (4 pages)
- Setra Model 206 (4 pages)
- Model 224 (8 pages)
- Model 231RS (16 pages)
- 260 (2 pages)
- 267MR (14 pages)
- Model 278 (2 pages)