2.0 INSTALLATION
2.1 Rough-In (see Fig 2.)
Install the SRMD in a 4 11/16” square electrical box. Run the power and signal
wiring into the box. Two wires are for the 24 VAC/DC power, and two wires are
for each of the signal lines from the field sensors to the display. For example,
the single display version would be 2 wires and the dual display needs 2 wires
for each of the two displays.
Run the wiring to the 24 VAC/DC source and to the sensors that are to be
monitored. The power to the sensors is not supplied by the displays.
2.2 Positioning the Front of the Electrical Box
It is very important that the box be set 1/16” to 1/8” below the finish wall so
that the faceplate will seal against the finished
wall.
If possible allow for ad-
justment at the finish stage to set the depth correctly.
Fig. 2
- Model ASM (8 pages)
- Model 204 (4 pages)
- Model 209 (4 pages)
- Model 227 (8 pages)
- 264 (4 pages)
- 269 (4 pages)
- Model 280E (4 pages)
- Model 370 (48 pages)
- Model 526 (7 pages)
- Model 540 (9 pages)
- Model 595 (8 pages)
- Model 869 (28 pages)
- Model 321 (4 pages)
- Model SRH (12 pages)
- Model Datum 2000 (31 pages)
- Model 217 (8 pages)
- Model 230 (12 pages)
- Model 242901-06 (1 page)
- Model 265 (4 pages)
- Model 270 (5 pages)
- Model 299 (4 pages)
- Model 470 (35 pages)
- Model 524 (6 pages)
- Model 546 (8 pages)
- Model 730 (16 pages)
- GCT-225 (8 pages)
- Model 141 (4 pages)
- Model 205-2 (4 pages)
- Model 223 (8 pages)
- Model 231 (12 pages)
- Model 256 (8 pages)
- Model 276 (2 pages)
- Model 3100 (8 pages)
- Model 516 (6 pages)
- Model 550 (9 pages)
- Model 760 (18 pages)
- Model LD330 (4 pages)
- Model 201 (4 pages)
- Setra Model 206 (4 pages)
- Model 224 (8 pages)
- Model 231RS (16 pages)
- 260 (2 pages)
- 267MR (14 pages)
- Model 278 (2 pages)