3 supply voltage adapters for the hc2 probes, Supply voltage adapters for the hc2 probes, E-m-hc2-accessories_24 – ROTRONIC HC2 User Manual
Page 4: 3supply voltage adapters for the hc2 probes
E-M-HC2-accessories_24
Rotronic AG
Bassersdorf, Switzerland
Document code
Unit
Accessories and Parts
for probes, indicators and transmitters
Instruction Manual
Document Type
Page 4 of 23
Document title
© 2009-2010; Rotronic AG E-M-HC2-accessories_23
3
Supply voltage adapters for the HC2 probes
Order Code
Description
E2-01XX-ACT
Female connector (black) with built-in voltage
regulator for HC2 probes.
1 m (3.2 ft) cable with tinned ends
See: Wiring color code
E2-02XX-ACT
Same as E2-01XX-ACT with 2m (6.5 ft) cable
E2-05XX-ACT
Same as E2-01XX-ACT with 5m (16.4 ft) cable
E3-01XX-ACT
Female connector (white) with built-in voltage
regulator for HC2 probes.
1 m (3.2 ft) cable with tinned ends
E3-02XX-ACT
Same as E3-01XX-ACT with 2m (6.5 ft) cable
E3-05XX-ACT
Same as E3-01XX-ACT with 5m (16.4 ft) cable
Specifications
Supply voltage to adapter
5…24 VDC / 5…16 VAC
Supply voltage to probe
3.3 VDC
Current consumption (includes HC2 probe)
< 4 mA
Wire color
Name
Function
Green
VDD (+)
VDC + or VAC Phase
Grey
GND
Power ground and digital signal ground
Red
RXD
UART
Blue
TXD
UART
White
Out 1 analog (+)
Humidity: 0…1 V = 0…100%RH (default)
or calculated parameter
Brown
Out 2 analog (+)
Temperature : 0…1V = -40…60°C (default)
Yellow
AGND (-)
Analog signal ground
Shielded cables with tinned ends: the shield is ended as a non-insulated wire connected to GND at the
connector level
NOTES: