IN-E-DS-U4WEB-V1_14

Rotronic AG
Bassersdorf, Switzerland

Document code

Unit

Docking station DS-U4WEB with web
server version 1: instruction manual

Instruction Manual

Document Type

Page

11 of 15

Document title

© 2007; Rotronic AG

IN-E-DS-U4WEB-V1_14

HTML

Description

Home.htm
(Current Values)

Rotronic Logo, firmware version, page navigator and current
measurement data for the inputs selected in the Web Server Settings
page. Automatic refresh rate: 60 seconds.

Messwerte.htm

This page is similar to Home.htm without Rotronic logo, firmware
version and page navigator. Automatic refresh rate: 60 seconds.

Probes.htm

Displays the current measurement data for all inputs (selected or not)
as unformatted text. (HTML)

Humi1 ... Humi7
(no extension)

Current humidity value for specified input (incl. unit) in text format

Temp1 … Temp7
(no extension)

Current temperature value for specified input (incl. unit) in text format

Calc1 … Calc7
(no extension)

Current calculated parameter value for specified input (incl. unit) in text
format

MesswerteChart.htm

Displays a bar graph for the parameter selected in the page header
table. The most recent 500 values (at the time the page was opened)
are displayed in the graph, based on the graph interval selected under
Settings. Bring the mouse cursor over the chart to see a data cursor
that displays the value, date and time of one data point at a time.

- Automatic scale
- No zoom function
- No automatic refresh

Note: the data underlying the chart is held in the docking station
volatile memory as opposed to the flash memory card of the data
logger. This data is lost when power is removed from the docking
station or when clicking on the apply button in the Web Server Settings
page.

Properties.htm

Displays the current configuration settings for both the data logger and
docking station. The settings can be changed from this page.

FreeFlash.htm

Displays the amount of free memory available on the data logger flash
card

Recording.htm

Displays the current settings of the data logger recording function. The
settings can be changed from this page