beautypg.com

Wiring for 4 to 20ma transmitter inputs, Wiring for optional inputs and outputs, Outputs – Dwyer 16L User Manual

Page 6

background image

949-1270

Page 6 of 28

December, 1998

Wiring for Optional Inputs and Outputs

Wire power and outputs as shown on page 5 and 6. Wiring for options is
shown opposite. All wiring shown below is Class 2. Shielded twisted pair
is required for Option 992.

Wiring for 4 to 20mA Transmitter inputs

Wire power and outputs as shown above. Two-wire transmitters wire as
shown below.

For three or four wire transmitters follow the wiring instructions provided
with your transmitter.

CAUTION: DO NOT WIRE THE 24 VOLT POWER SUPPLY

ACROSS THE INPUT OF THE CONTROL. DAMAGE TO

THE CONTROL INPUT CIRCUITRY WILL RESULT.

OUTPUTS

Output A

Output B

+ -

+ -

Power Supply

15 to 28 VDC

+

-

Transmitter

+

-

-

+

For relay, NO (Order Code 3) or SSR (Order
Code 1) outputs, 15 & 16 and 17 & 18 are
Normally Open.

For relay, NC (Order Code 4) outputs, 15 & 16
and 17 & 18 are Normally Closed.

For Pulsed DC (Order Code 2) and DC SSR
(Order Code 8) outputs, 15 & 17 are positive
and 16 & 18 are negative.