SPECIFICATIONS

Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current

selectable.

Input Impedance:

Thermocouple = 3 megohms minimum.

RTD current = 200 µA.

Current = 10 ohms.

Voltage = 5000 ohms.

Sensor Break Protection: De-energizes output(s) to protect system after

customer set time. (See InPt in Secondary Menu.)

Set Point Range: Selectable (See Range Chart Page 26).

Display: Two 4 digit, 7 segment 0.3" high LEDs.

Output Action: Fully programmable to allow output(s) to energize or de-

energize above or below set point(s).

On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F,

1° C, or 1 count steps.

Accuracy: ±0.25% of span, ±1 least significant digit.

Resolution: 1 degree or 0.1 degree, selectable.

Line Voltage Stability: ±0.05% over the supply voltage range.

Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F)

maximum (100 ppm / °C typical, 200 ppm / °C maximum).

Common Mode Rejection: 140 db minimum at 60 Hz.

Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.

Isolation:

Relay and SSR outputs: 1500 Vac to all other inputs and outputs.

SP1 and SP2 Switched Voltage outputs: 500 Vac to all other inputs

and outputs, but not isolated from each other.

Process Output (934, 936): 500 VAC to all other inputs and outputs.

Supply Voltage: 100 to 240 Vac, nominal., +10 -15%, 50 to 400 Hz. single

phase; 132 to 240 Vdc, nominal., +10 -20%.

Supply Voltage (Option 9502):

12 to 24 Vdc, Vac 40-400 Hz, ±20%.

Power Consumption: 5VA maximum.

Operating Temperature: -10 to +55 °C (+14 to 131 °F).

Storage Temperature: -40 to +80 °C (-40 to 176 °F).

Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at

55 °C non-condensing.

Memory Backup: Nonvolatile memory. No batteries required.