Dwyer 16L User Manual
Page 20
949-1270
Page 20 of 28
December, 1998
S1St
Set Point 1 State: Select Eng or dEng.
Eng
Output Energized. The output device (per Order Code)
will be energized at set point. (Normally Open contacts
will close, Normally Closed contacts will open.)
dEng
Output De-energized. The output device (per Order
Code) will be de-energized at set point. (Normally Open
contacts will open, Normally Closed contacts will close.)
S1LP
Set Point Lamp: Select O on or OoFF.
O on
Lamp ON when Output is ON (energized).
OoFF
Lamp OFF when Output is ON (energized).
If your instrument is not equipped with Set Point 2, then proceed to
the option section (next page). If the instrument has no Set Point 2 and
no options, then the menu ends.
S2t
Set Point 2 type: Select Abs or dE.
AbS
Absolute SP2. SP2 is independent of SP1, and may be set
anywhere between the limits of SPL and SPH.
dE
Deviation SP2. SP2 is set as a deviation from SP1, and
allows SP2 to retain its relationship with SP1 when SP1 is
changed (tracking SP2).
S2F
Set Point 2 Function: Select Hi of Lo.
Hi
Output is energized above set point.
Lo
Output is energized below set point.
S2rE
Set Point 2 Reset. Select OnOF or Hold.
OnOF
Control will automatically reset when process passes
back through SP2d.
HoLd
Manual Reset. Reset (acknowledge) by pressing the
LIMIT RESET key for 3 seconds.
S2Pi
Set Point 2 Power Interrupt. Select On or OFF.
On
Alarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFF
Alarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S2iH
Set Point 2 Inhibit: Select On or OFF.
On
Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF
Alarm Inhibit is OFF.