SECURE MENU
Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to advance to the
next menu item. Press UP ARROW or DOWN ARROW to change the value
in the display. Press ENTER to retain the value.
OUTPUTS ARE DISABLED (TURNED OFF) WHILE CONTROL IS IN
SECURE MENU.

SECr

Security Code: See the Security Level Selection and the Password
Table in this manual, in order to enter the correct password.

InP

Input Type: Select one of the following. Refer to the Input wiring
section for the proper wiring.

J-IC

Type “J” Thermocouple

CA

Type “K” Thermocouple

E-

Type “E” Thermocouple

t-

Type “T” Thermocouple

L-

Type “L” Thermocouple

n-

Type “N” Thermocouple

r-13

Type “R” Thermocouple

S-10

Type “S” Thermocouple

b-

Type “B” Thermocouple

C-

Type “C” Thermocouple

P392

100 ohm Platinum (NIST 0.00392

Ω/Ω

/°C)

n120

120 ohm Nickel

P385

100 ohm Platinum (DIN 0.00385

Ω/Ω

/°C)

1P38

1000 ohm Platinum (DIN 0.00385

Ω/Ω

/°C)

Curr

DC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.

UoLt

DC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.

diFF

DC Voltage Input -10 to +10 mV.

- - - -

Reserved

OSUP

Zero Suppression: Select On or OFF. Only with Current and Voltage

input types.

OFF

The input range will start at 0 (zero) Input.

On

The input range will start at 4.00 mA or 2.00 V.

Unit

F, C or None.
F

°F descriptor is On and temperature inputs will be dis-
played in actual degrees Fahrenheit.

C

°C descriptor is On and temperature inputs will be dis-
played in actual degrees Celsius.

nonE

°F and °C descriptors will be Off. This is only available with
Current and Voltage Inputs.