Secure menu – Dwyer 16L User Manual
Page 17
December, 1998
Page 17 of 28
949-1270
SECURE MENU
Hold UP ARROW & ENTER for 5 Seconds. Press INDEX to advance to the
next menu item. Press UP ARROW or DOWN ARROW to change the value
in the display. Press ENTER to retain the value.
OUTPUTS ARE DISABLED (TURNED OFF) WHILE CONTROL IS IN
SECURE MENU.
SECr
Security Code: See the Security Level Selection and the Password
Table in this manual, in order to enter the correct password.
InP
Input Type: Select one of the following. Refer to the Input wiring
section for the proper wiring.
J-IC
Type “J” Thermocouple
CA
Type “K” Thermocouple
E-
Type “E” Thermocouple
t-
Type “T” Thermocouple
L-
Type “L” Thermocouple
n-
Type “N” Thermocouple
r-13
Type “R” Thermocouple
S-10
Type “S” Thermocouple
b-
Type “B” Thermocouple
C-
Type “C” Thermocouple
P392
100 ohm Platinum (NIST 0.00392
Ω/Ω
/°C)
n120
120 ohm Nickel
P385
100 ohm Platinum (DIN 0.00385
Ω/Ω
/°C)
1P38
1000 ohm Platinum (DIN 0.00385
Ω/Ω
/°C)
Curr
DC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.
UoLt
DC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.
diFF
DC Voltage Input -10 to +10 mV.
- - - -
Reserved
OSUP
Zero Suppression: Select On or OFF. Only with Current and Voltage
input types.
OFF
The input range will start at 0 (zero) Input.
On
The input range will start at 4.00 mA or 2.00 V.
Unit
F, C or None.
F
°F descriptor is On and temperature inputs will be dis-
played in actual degrees Fahrenheit.
C
°C descriptor is On and temperature inputs will be dis-
played in actual degrees Celsius.
nonE
°F and °C descriptors will be Off. This is only available with
Current and Voltage Inputs.