Bulletin E-73

Specifications - Installation and Operating Instructions

Float Switch

W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.

P.O. BOX 358 • MICHIGAN CITY, INDIANA 46360 U.S.A.

Phone: 219/879-8000

www.dwyer-inst.com

Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS
Service:
Liquids compatible with wetted materials.
Wetted Materials:

Float and Rod: 316 SS;
Body: Brass or 316 SS standard;
Magnet Keeper: 430 SS standard, 316 SS or nickel optional.

Temperature Limits: 4 to 275°F (-20 to 135°C) standard, MT high
temperature option 400°F (205°C) [MT option not UL, CSA, ATEX, or
SAA]. ATEX and IECEx options, ambient temperature -4 to 163°F (-20 to
73°C); Process temperature -4 to 163°F (-20 to 73°F).
Pressure Limit: Brass body 1000 psig (69 bar), 316 SS body 2000 psig
(138 bar). Standard float rated 100 psig (6.9 bar). For other floats see
model chart on next page.
Enclosure Rating: Weatherproof and Explosion-proof. Listed with UL
and CSA for Class I, Groups C and D; Class II, Groups E, F, and G.
ATEX 0344 II 2 G Ex d IIB T6 Gb -20°C≤Tamb≤73°C.
-20°C≤Process Temp≤73°C. Alternate Temperature Class T5 Process
Temp ≤88°C, T4 Process Temp ≤123°C, 145°(T3) Process Temp ≤133°C
consult factory.
EC-Type Certificate No.: KEMA 03 ATEX 2383
ATEX Standards: EN60079-0: 2009;

EN60079-1: 2007.

IECEX Certified: For Ex d IIB T6 Gb -20°C≤Tamb≤73°C.
-20°C≤Process Temp≤73°C. Alternate Temperature Class T5 Process
Temp ≤88°C, T4 Process Temp ≤123°C, 145°(T3) Process Temp ≤133°C
consult factory.
IECEX Certificate of Conformity: IECEX DEK 11.0071
IECEX Standards: IEC 60079-0: 2007; IEC60079-1: 2007
SAA: Exd II C T6 (T amb = 60°C).
Alternate Ratings: T5 (T amb = 75°C) T4 (T amb = 110°C) alternate “T”
ratings may be provided.
IP66 C1 I, Zone I. Also FM approved.
Switch Type: SPDT snap switch standard, DPDT snap switch optional.
Electrical Rating: UL, FM, ATEX and SAA models: 10A @ 125/250 VAC
(V~). CSA models: 5A @ 125/250 VAC (V~); 5A res., 3A ind. @ 30 VDC
(V ). MV option: 1A @ 125 VAC (V~); 1A res., .5A ind. @ 30 VDC (V ).
MT option: 5A @ 125/250 VAC (V~). [MT and MV option not UL, CSA, FM,
ATEX or SAA].
Electrical Connections: UL and CSA models: 16 AWG, 6˝ (152 mm)
long. ATEX and SAA unit: terminal block.
Process Connection: 1-1/2˝ male NPT standard, 2-1/2˝ male NPT
standard optional floats.
Mounting Orientation: Horizontal installation standard, optional vertical
top mount.
Weight: 4 lb 9 oz (2.07 kg).
Dead Band: 3/4˝ (19 mm) for standard float.
Specific Gravity: 0.7 minimum with standard float. For other floats see
model chart.

Series L4

Rugged and reliable the Flotect

®

L4 Level switch operates

automatically to indicate tank level. Perfect for starting or stopping
pumps, opening or closing valves, or actuate level alarm signals. A
unique magnetically actuated switching design gives superior
performance. There are no bellows, springs, or seals to fail. Instead, the
free-swinging float attracts a magnet within the solid metal switch body,
actuating a snap switch by means of a simple lever arm. Float arm hinge
design limits the arm angle to prevent vertical hangup.

FEATURES
• Leak proof body machined from bar stock
• Choice of floats dependent on maximum pressure and specific gravity
• Weatherproof, designed to meet NEMA 4
• Explosion-proof (listings included in specifications)
• Installs directly and easily into tank with a thredolet or flange

(see application drawings on page 4)

• Electrical assembly can be easily replaced without removing the unit

from the installation so that the process does not have to be shut down

• Horizontal installation or optional top mount vertical installation

APPLICATIONS
• Direct pump control for maintaining level
• Automatic tank dump operations
• Control levels or provide alarms in sumps, scrubber systems, hydro-

pneumatic tanks, low pressure boilers, and various waste
water/sewage treatment processes

IOM Guideline L4 ATEX