Dwyer 16L User Manual
Page 19
December, 1998
Page 19 of 28
949-1270
SCAH
Scale High: Select 100 to 9999 counts above SCAL. The total span
between SCAL and SCAH must be within 11998 counts. Maximum
setting range is -1999 to +9999 counts. For Current and Voltage
inputs, this will set the high range end. Viewable only for Thermo-
couple and RTD ranges.
SPL
Set Point Low: Select from the lowest input range value to SPH
value. This will set the minimum SP1 or SP2 value that can be
entered. The value for SP1 or SP2 will not stop moving when this
value is reached.
SPH
Set Point High: Select from the highest input range value to SPL
value. This will set the maximum SP1 or SP2 value that can be
entered. The value for SP1 or SP2 will not stop moving when this
value is reached.
SP1O
Set Point 1 Output Select: Select A or A-b.
A
Set Point 1 is routed through Output A, Set Point 2 (if
equipped) is routed through Output B.
A-b
Set Point 1 is routed through both Output A and Output
B. Set Point 2 menu items are suppressed. This allows
for both NO and NC (Order Code types 3 and 4) outputs
to be driven at the same time.
S1F
Set Point 1 Function: Select Hi or Lo.
Hi
Output is energized above set point.
Lo
Output is energized below set point.
S1rE
Set Point 1 Reset. Select OnOF or Hold.
OnOF
Control will automatically reset when process passes
back through SP1d.
HoLd
Manual Reset. Reset (acknowledge) by pressing the
LIMIT RESET key for 3 seconds.
S1Pi
Set Point 1 Power Interrupt. Select On or OFF.
On
Alarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFF
Alarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S1iH
Set Point 1 Inhibit: Select On or OFF.
On
Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF
Alarm Inhibit is OFF.