Page 21 – Dwyer 4C User Manual
Page 21
Page 21
Thermocouple Type and Temperature Range
Input Temperature Sensor Type
LED Display Temperature Range
Thermocouple TXK type
-328 ~ 1440°F (-200 ~ 800°C)
Thermocouple U type
-328 ~ 932°F (-200 ~ 500°C)
Thermocouple L type
-328 ~ 1562°F (-200 ~ 850°C)
Thermocouple B type
212 ~ 3272°F (100 ~ 1800°C)
Thermocouple S type
32 ~ 3092°F (0 ~ 1700°C)
Thermocouple R type
32 ~ 3092°F (0 ~ 1700°C)
Thermocouple N type
-328 ~ 2340°F (-200 ~ 1300°C)
Thermocouple E type
32 ~ 1112°F (0 ~ 600°C)
Thermocouple T type2
-4 ~ 752°F (-20 ~ 400°C)
Thermocouple T type1
-328 ~ 752°F (-200 ~ 400°C)
Thermocouple J type2
-4 ~ 752°F (-20 ~ 400°C)
Thermocouple J type1
-148 ~ 1562°F (-100 ~ 850°C)
Thermocouple K type2
-4 ~ 932°F (-20 ~ 500°C)
Thermocouple K type1
-328 ~ 2340°F (-200 ~ 1300°C)
RTD Type and Temperature Range
Input Temperature Sensor Type
LED Display Temperature Range
Platinum Resistance (Pt100) type 3
32 ~ 212°F (0 ~ 100°C)
Platinum Resistance (Pt100) type 2
-4 ~ 932°F (-20 ~ 500°C)
Platinum Resistance (Pt100) type 1
-328 ~ 1112°F (-200 ~ 600°C)
Platinum Resistance (JPt100) type 2
32 ~ 212°F (0 ~ 100°C)
Platinum Resistance (JPt100) type 1
-4 ~ 752°F (-20 ~ 400°C)