Communication Register List
Communication Parameters List
Controller offers a RS-485 port for serial communication.
1.
Supporting transmission speed: 2400, 4800, 9600, 19200, 38400 bps.
2. Communication protocol: Modbus (ASCII).
3.
Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2.
4. Available communication address: 1 to 255, 0 is broadcast address.
5.
Function code: 03H to read the contents of register (Max. 3 words).
6.
06H to write 1 (one) word into register.
Address Content
Explanation
4700H (R) Process value (PV)
Measuring unit is 0.1, updated one time
in 0.5 second.
4701H
Set point (SV)
Unit is 0.1, oC or oF
4702H
Upper-limit alarm 1
4703H
Lower-limit alarm 1
4704H
Upper-limit alarm 2
4705H
Lower-limit alarm 2
4706H
Upper-limit of temperature range The data content should not be higher than
the temperature range
4707H
Lower-limit of temperature range The data content should not be lower than
the temperature range
4708H
PB Proportional band
0.1 to 999.9, unit is 0.1
4709H
Ti Integral time
0 to 9999
470AH
Td Derivative time
0 to 9999
470BH
Heating/Cooling hysteresis
0 to 9999
470CH ~ 470FH
Reserved
4710H
Input temperature sensor type
Please refer to the contents of the
“Temperature Sensor Type and
Temperature Range” for detail
4711H
Control method
0: PID (default), 1: ON/OFF, 2: manual tuning
4712H
Heating/Cooling control cycle
1 to 99 second
4713H
Proportional control
0% to 100%
offset error value
4714H
Temperature regulation value
-999 ~ 999, unit: 0.1
4715H
Alarm 1 type
Please refer to the contents of the “Alarm
Outputs” for detail
4716H
Alarm 2 type
Please refer to the contents of the “Alarm
Outputs” for detail
4717H
Temperature unit display selection oC: 1 (default), oF: 0
4718H
Heating/Cooling control Selection Heating: 0 (default), Cooling: 1
4719H
Control Run/Stop setting
Run: 1 (default), Stop: 0
471AH
Communication write-in selection Communication write in disabled: 0 (default),
Communication write in enabled: 1
471BH
Software version
W1.00 indicates 0 x 100
4729H
AT Setting
OFF: 0 (default), ON:1
Code 0
Normal operation (No error)
Code 1
Initial process
Code 2
Initial status (Temperature is not stable)
Code 3
Temperature sensor is not connected
472BH (R) Code 4
Temperature sensor input error
Code 5
Measured temperature value exceeds
the temperature range
Code 6
No Int. error
Code 7
EEPROM Error
4733H
CT monitor value
Unit is 0.1A
Note: R means “read only” value