Communication Register List

Communication Parameters List
Controller offers a RS-485 port for serial communication.
1.

Supporting transmission speed: 2400, 4800, 9600, 19200, 38400 bps.

2. Communication protocol: Modbus (ASCII).
3.

Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2.

4. Available communication address: 1 to 255, 0 is broadcast address.
5.

Function code: 03H to read the contents of register (Max. 3 words).

6.

06H to write 1 (one) word into register.

Address Content

Explanation

4700H (R) Process value (PV)

Measuring unit is 0.1, updated one time
in 0.5 second.

4701H

Set point (SV)

Unit is 0.1, oC or oF

4702H

Upper-limit alarm 1

4703H

Lower-limit alarm 1

4704H

Upper-limit alarm 2

4705H

Lower-limit alarm 2

4706H

Upper-limit of temperature range The data content should not be higher than

the temperature range

4707H

Lower-limit of temperature range The data content should not be lower than

the temperature range

4708H

PB Proportional band

0.1 to 999.9, unit is 0.1

4709H

Ti Integral time

0 to 9999

470AH

Td Derivative time

0 to 9999

470BH

Heating/Cooling hysteresis

0 to 9999

470CH ~ 470FH

Reserved

4710H

Input temperature sensor type

Please refer to the contents of the
“Temperature Sensor Type and
Temperature Range” for detail

4711H

Control method

0: PID (default), 1: ON/OFF, 2: manual tuning

4712H

Heating/Cooling control cycle

1 to 99 second

4713H

Proportional control

0% to 100%

offset error value

4714H

Temperature regulation value

-999 ~ 999, unit: 0.1

4715H

Alarm 1 type

Please refer to the contents of the “Alarm
Outputs” for detail

4716H

Alarm 2 type

Please refer to the contents of the “Alarm
Outputs” for detail

4717H

Temperature unit display selection oC: 1 (default), oF: 0

4718H

Heating/Cooling control Selection Heating: 0 (default), Cooling: 1

4719H

Control Run/Stop setting

Run: 1 (default), Stop: 0

471AH

Communication write-in selection Communication write in disabled: 0 (default),

Communication write in enabled: 1

471BH

Software version

W1.00 indicates 0 x 100

4729H

AT Setting

OFF: 0 (default), ON:1

Code 0

Normal operation (No error)

Code 1

Initial process

Code 2

Initial status (Temperature is not stable)

Code 3

Temperature sensor is not connected

472BH (R) Code 4

Temperature sensor input error

Code 5

Measured temperature value exceeds
the temperature range

Code 6

No Int. error

Code 7

EEPROM Error

4733H

CT monitor value

Unit is 0.1A

Note: R means “read only” value