Mpm, apm, ppm, & lti series modbus, Register tables serial communication – Dwyer PPM User Manual
Page 8
MPM, APM, PPM, & LTI Series Modbus
®
Register Tables
Serial Communication
Page 8
Register
1
Name Access
Limits or
Range
2
Units
Data
Type
3
Function
Code(s)
Comments
Number Address
(hex)
40072 – 40073
71 – 72
(0047 – 0048)
Modbus Big
Display value
Read Write
-99999 to
+999999
User defined
Long Hi
Long Lo
03, 04,
06, 16
Represents the Modbus Big display value excluding the decimal
point. Register 40088 contains the decimal point.
Set Register 40070 = 0, Register 40117 = 18
40074 – 40075
73 – 74
(0049 – 004A)
Modbus Little
Display value
Read Write
-99999 to
+999999
User defined
Long Hi
Long Lo
03, 04,
06, 16
Represents the Modbus Little display value excluding the
decimal point. Register 40089 contains the decimal point.
Register 40071 = 0, Register 40118 = 18
40076
75
(004B)
Modbus Big
Display MSD
value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Big Display MSD (Most Significant
Digit) value. The hex value represents the allowable ASCII
character, see Table 7.
Register 40117 = 18
Register 40070 = 1 for registers 40076-81.
Register 40088 contains the decimal point.
40077
76
(004C)
Modbus Big
Display MSD-1
value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Big Display MSD-1 value. The hex
value represents the allowable ASCII character.
40078
77
(004D)
Modbus Big
Display MSD-2
value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Big Display MSD-2 value. The hex
value represents the allowable ASCII character.
40079
78
(004E)
Modbus Big
Display MSD-3
value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Big Display MSD-3 value. The hex
value represents the allowable ASCII character.
40080
79
(004F)
Modbus Big
Display MSD-4
value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Big Display MSD-4 value. The hex
value represents the allowable ASCII character.
40081
80
(0050)
Modbus Big
Display MSD-5
(LSD) value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Big Display MSD-5 (which is the LSD)
value. The hex value represents the allowable ASCII character.
40082
81
(0051)
Modbus Little
Display MSD
value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Little Display MSD (Most Significant
Digit) value. The hex value represents the allowable ASCII
character, see Table 7.
Register 40118 = 18
Register 40071 = 1 for registers 40082-87.
Register 40089 contains the decimal point.
40083
82
(0052)
Modbus Little
Display MSD-1
value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Little Display MSD-1 value. The hex
value represents the allowable ASCII character.
40084
83
(0053)
Modbus Little
Display MSD-2
value
Read Write
Not applicable
None
Byte
03, 04,
06, 16
Represents the Modbus Little Display MSD-2 value. The hex
value represents the allowable ASCII character.