MPM, APM, PPM, & LTI Series Modbus
®
Register Tables
Serial Communication
Page 14
Register
1
Name Access
Limits or
Range
2
Units
Data
Type
3
Function
Code(s)
Comments
Number Address
(hex)
40169
168
(00A8)
Programmable
User Digital
Output 7 Setting
Read Write
0 to 20
User defined
Integer
03, 04,
06, 16
See Table 3.
40170
169
(00A9)
Programmable
User Digital
Output 8 Setting
Read Write
0 to 20
User defined
Integer
03, 04,
06, 16
See Table 3.
40171 – 40172
170 – 171
(00AA-00AB)
Password 1
Read Write 000000 to 999999
None
Floating point
03, 04,
06, 16
See Note 4.
40173 – 40174
172 – 173
(00AC-00AD)
Password 2
Read Write 000000 to 999999
None
Floating point
03, 04,
06, 16
See Note 4.
40175 – 40176
174 – 175
(00AE-00AF)
Password 3
Read Write 000000 to 999999
None
Floating point
03, 04,
06, 16
See Note 4.
40177 – 40178
176 – 177
(00B0 – 00B1)
Total Password Read Write 000000 to 999999
None
Floating point
03, 04,
06, 16
See Note 4.
40179 – 40180
178 – 179
(00B2 – 00B3)
Grand Total
Password
Read Write 000000 to 999999
None
Floating point
03, 04,
06, 16
See Note 4.
40181
180
(00B4)
PV2 Decimal
Point
Read Write
0 to 5
None
Integer
03, 04,
06, 16
Selects based on number of digits to the right of the decimal
point (e.g. 0 = no decimal point and 5 = d.ddddd).
40182
181
(00B5)
PV2 Number of
Points
Read Write
2 to 8
None
Integer
03, 04,
06, 16
This register is only used when register 40137 is set to Linear.
40183 – 40184
182 – 183
(00B6 – 00B7)
PV2 Display
Value
Read Only -99999 to 999999
User defined
Floating point
03, 04
Represents the PV2 display value including the decimal point.
Under Range = -99999, Over Range = 999999, and
Open = -99999
40185
184
(00B8)
PV2 Display
value
Read Only -99999 to 999999
User defined
Long Hi
03, 04
Represents the display value excluding the decimal point.
Decimal point setting in 40181.
40186
185
(00B9)
PV2 Display
value
Read Only
User defined
Long Lo
03, 04
Must be read with 40185.
40187
186
(00BA)
PV1% Display
value
Read Only
-100 to 100
User defined
Integer
03, 04
Represents the PV1% display value.
40301
300
(012C)
Relay 1 Mode Read Write
Not applicable
None
Word; bits
03, 04,
06, 16
See Table 4 for operating modes and bit assignments.
40302 – 40303
301 – 302
(012D – 012E)
Relay 1
Set Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40304 – 40305
303 – 304
(012F – 0130)
Relay 1
Reset Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40306
305
(0131)
Relay 1
On Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16