MPM, APM, PPM, & LTI Series Modbus
®
Register Tables
Serial Communication
Page 16
Register
1
Name Access
Limits or
Range
2
Units
Data
Type
3
Function
Code(s)
Comments
Number Address
(hex)
40335 – 40336
334 – 335
(014E – 014F)
Relay 4 Sample
Time
Read Write
0 to 59999
1/10 of Seconds Floating point
03, 04,
06, 16
40337
336
(0150)
Relay 5 Mode Read Write
Not applicable
None
Word; bits
03, 04,
06, 16
See Table 4 for operating modes and bit assignments.
40338 – 40339
337 – 338
(0151 – 0152)
Relay 5
Set Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40340 – 40341
339 – 340
(153 – 0154)
Relay 5
Reset Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40342
341
(0155)
Relay 5
On Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40343
342
(0156)
Relay 5
Off Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40344 – 40345
343 – 344
(0157 – 0158)
Relay 5 Sample
Time
Read Write
0 to 59999
1/10 of Seconds Floating point
03, 04,
06, 16
40346
345
(0159)
Relay 6 Mode Read Write
Not applicable
None
Word; bits
03, 04,
06, 16
See Table 4 for operating modes and bit assignments.
40347 – 40348
346 – 347
(015A – 015B)
Relay 6
Set Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40349 – 40350
348 – 349
(015C – 015D)
Relay 6
Reset Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40351
350
(015E)
Relay 6
On Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40352
351
(015F)
Relay 6
Off Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40353 – 40354
352 – 353
(0160 – 0161)
Relay 6 Sample
Time
Read Write
0 to 59999
1/10 of Seconds Floating point
03, 04,
06, 16
40355
354
(0162)
Relay 7 Mode Read Write
Not applicable
None
Word; bits
03, 04,
06, 16
See Table 4 for operating modes and bit assignments.
40356 – 40357
355 – 356
(0163 – 0164)
Relay 7
Set Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40358 – 40359
357 – 358
(0165 – 0166)
Relay 7
Reset Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40360
359
(0167)
Relay 7
On Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40361
360
(0168)
Relay 7
Off Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40362 – 40363
361 – 362
(0169 – 016A)
Relay 7 Sample
Time
Read Write
0 to 59999
1/10 of Seconds Floating point
03, 04,
06, 16