Register
1
Name Access
Limits or
Range
2
Units
Data
Type
3
Function
Code(s)
Comments
Number Address
(hex)
40307
306
(0132)
Relay 1
Off Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40308 – 40309
307 – 308
(0133 – 0134)
Relay 1 Sample
Time
Read Write
0 to 59999
1/10 of Seconds Floating point
03, 04,
06, 16
40310
309
(0135)
Relay 2 Mode Read Write
Not applicable
None
Word; bits
03, 04,
06, 16
See Table 4 for operating modes and bit assignments.
40311 – 40312
310 – 311
(0136 – 0137)
Relay 2
Set Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40313 – 40314
312 – 313
(0138 – 0139)
Relay 2
Reset Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40315
314
(013A)
Relay 2
On Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40316
315
(013B)
Relay 2
Off Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40317 – 40318
316 – 317
(013C – 013D)
Relay 2 Sample
Time
Read Write
0 to 59999
1/10 of Seconds Floating point
03, 04,
06, 16
40319
318
(013E)
Relay 3 Mode Read Write
Not applicable
None
Word; bits
03, 04,
06, 16
See Table 4 for operating modes and bit assignments.
40320 – 40321
319 – 320
(013F – 0140)
Relay 3
Set Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40322 – 40323
321 – 322
(0141 – 0142)
Relay 3
Reset Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40324
323
(0143)
Relay 3
On Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40325
324
(0144)
Relay 3
Off Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40326 – 40327
325 – 326
(0145 – 0146)
Relay 3 Sample
Time
Read Write
0 to 59999
1/10 of Seconds Floating point
03, 04,
06, 16
40328
327
(0147)
Relay 4 Mode Read Write
Not applicable
None
Word; bits
03, 04,
06, 16
See Table 4 for operating modes and bit assignments.
40329 – 40330
328 – 329
(0148 – 0149)
Relay 4
Set Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40331 – 40332
330 – 331
(014A – 014B)
Relay 4
Reset Point
Read Write -99999 to 999999
User defined
Floating point
03, 04,
06, 16
40333
332
(014C)
Relay 4
On Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,
06, 16
40334
333
(014D)
Relay 4
Off Delay
Read Write
0 to 1999
1/10 of Seconds
Integer
03, 04,