beautypg.com

Dwyer BFM User Manual

Page 5

background image

SOUNDING AN ALARM TO INDICATE DECREASED
FLOW:

An alarm will sound when flow drops below the preset amount
(Fig. 11):

• When flow drops the relay contacts close to energize the

alarm.

• The power to the alarm (connected to the COM terminal) is

from the motor starter circuit so the alarm can only sound
when the motor is running. When the motor Stop button is
pressed the alarm will silence.

MACHING

SUPPLYING

MATERIAL

MOTOR

STARTER

START

SWITCH

TB2

COM

N/0

N/C

AC COM

117VAC

ALARM

NOTE: AUXILLARY SET OF

NORMALLY CLUSED

CONCACTS (CLOSED WHEN

STARTER IS ENERGIZED).

SHUTTING DOWN EQUIPMENT WHEN FLOW
DECREASES:

Equipment shut down mode is required if the flow rate drops
below the preset level. The relay is often wired to stop the
equipment that is supplying the material (Fig. 12 and 13).

STOP

START

STARTER

COIL

NORMAL STARTER CIRCUIT

Before the “controlled” equipment can be started again, the
following must occur:

• Material is flowing past the BFS-1 sensor.
• The Green L.E.D. (FLOW) indicator light is lit indicating

material flow.

• You may have to hold down the Start button until flow

reaches the preset rate.

As long as material continues to flow past the BFS-1 sensor
above the preset rate, the machine equipment supplying mate-
rial will continue to run. If the rate of material flow falls below
the preset level, the relay will open and the machine equip-
ment supplying the material will stop.

STOP

START

STARTER

COIL

TB2

COM

N / 0

M / C

STARTER CIRCUIT WITH BFM SHUTDOWN

Figure 11

Figure 12

Figure 13

FL-1-BFM:TEMPLATE 12/4/08 10:59 AM Page 5