3/4˝ HIGH

VOLTAGE INPUT

1/2˝ LOW

VOLTAGE INPUT

BFM WIRING
The BFM polycarbonate housing comes with 10 PG conduit
knockouts in the housing.

• High voltage inputs above 24 volt AC should be routed into

the housing through the 3/4˝ (20mm) conduit hole.

• All Low voltage wiring (TTL, RS232, and sensor) should be

routed through the 1/2˝ (14mm) conduit hole.

HIGH VOLTAGE INPUTS

Connect the 120VAC, 50/60 HZ, 1 Amp supply on TB2
terminals (Fig. 2):

• 120VAC (Hot) supply to 117VAC terminal (or 12VDC, 240VAC

per the model)

• AC Common to AC COM terminal
• Earth-Ground to E GND terminal. Must connect to prevent

accidental electrical shock.

• A 1-Amp fuse is located next to the transformer.

SENSOR INPUTS
Connect the low voltage Flow Sensor to the Sensor terminals
TB1 (Fig. 4):

• Positive RED (or White) sensor lead to the “+” Sensor

terminal on TB1.

• Negative BLACK sensor lead to the “-” Sensor terminal on

TB1.

The sensor wiring should be a minimum of 18 AWG strand-
ed 2-conductor cable. Use 18 AWG for up to 500´ (155m) and
16 GA up to 2000' (620m).

• All Sensor wire splices must be SOLID and WATER TIGHT.

Figure 1

Figure 2

Figure 3

Figure 4