beautypg.com

Dwyer IEFS User Manual

Page 6

background image

Page 9

CONNECTIONS DIAGRAMS

Grounding Guidelines:

For best results, use a good quality earth ground, such as
metallic water piping or a driven ground, to ensure a good
connection to earth ground and good noise suppression.

For Metallic Pipe:

For optimum connection, clamp wire to the

piping a short distance to one side of the flow sensor using an
electrical grounding clamp. Connect the wire to the earth ground
and to one of the housing screws, as shown in “Grounding
Diagram” below.

For Non-Metallic Pipe:

Connect a wire from the housing screws

to a good earth ground, such as metalic water piping or a rod
driven into the ground.

Series IEFS & EFS2 meters are usually unaffected by moderate
levels of electrical noise. In some applications performance
may be improved by taking the following steps:

• Use shielded twisted pair cable (Belden 8723 or

equivalent above ground or Alpha 35482 or

equivalent burial).

• Clamp a ferrite bead (Steward 28A2029-OAO or

equivalent) on meter signal/power wire within 3/4”

of the meter strain relief (tape or tie wrap in place if

necessary). See diagram below.

• IMPORTANT - Connect the cable shield ground

wire to ground, ONLY at power supply end of cable.

General Electrical Guidelines:

• Whenever possible, avoid running control cables in

the same conduit with or bundled with AC power.

• Using shielded cable, be sure to connect shield to

ground at power supply end of the cable. Do not
connect other end of shield.

• Avoid routing flow sensor cables in close proximity to

a variable frequency drive.

• Recommended power and output wiring is shielded

twisted pair 18 to 22 AWG control cable.

• Recommended voltage is 12 to 24 VDC. Note that

unregulated power supplies can vary from nameplate
voltage by a considerable amount, especially with AC
line voltage fluctuation. Therefore 24V power supplies
must be regulated.

See the Connections diagrams on the following pages for the
appropriate terminals.

Power:

A 12 to 24 Vdc power supply capable of at least 250

mA current output is needed.

Output:

The standard output is pulses with flow in the forward

direction (Reverse flow output is optional (-RFO ). Electrically
it is an open collector opto isolated switch. The output is not
internally powered.

Note:

This output is limited to 6 mA at 30 Vdc maximum.

COuNTER OR PLC

bAT 4 to 20 mA OuTPuT

Power

Forward Output

(open collector)

Reverse Output

( -RFO only)

12 to 24 VDC

Max. 6 mA, 30 VDC

Power

Forward Output

SERIES IEFS

SERIES bAT

SERIES IEFS

Sensor

4 to 20 mA

4 to 20 mA

24 VDC Power

Reverse Output

(-RFO only)

+

Max. 6 mA 30 VDC

*See Dual RTI Diagram for an

example of bidirectional connections.

FREquENCy

*See Dual RTI Diagram for an

example of bidirectional connections.

COuNTER OR PLC DIGITAL

INPuT

Page 8

ELECTRICAL CONNECTIONS

GROuNDING DIAGRAM

housing Screw

Earth

Ground

Grounding Clamp

24 VDC Power

PLACE FERRITE bEAD hERE

Metallic Pipe