iNsTALLATiON

caution:

These flow sensors are not recommended for installation down-

stream of the boiler feedwater pump where installation fault may expose the

flow sensor to boiler pressure and temperature. Maximum recommended

temperature is 200°F.

FULL PiPe recOMMeNDATiONs

recOMMeNDeD

NOT recOMMeNDeD

recOMMeNDeD

NOT recOMMeNDeD

Allows air pockets to form at sensor

Ensures full pipe

Post-valve cavitation can create air pocket

Keeps pipe full at sensor

Air can be trapped

Allows air to bleed off

recOMMeNDeD

NOT recOMMeNDeD

Page 7

Page 6

cONNecTiON

cONNecTiON

Sensors are supplied with 18 ft. of cable. For sensors with

no additional electronics, see diagram for color coding of

connections. For sensors with on-board electronics, see the

manual accompanying the electronic module.

calibration (“K-Factor”).

In order to properly process pulses from

the flow sensor, a number must be entered into the control to

which the sensor is connected. This number, called the K-factor,

is the number of pulses the sensor puts out per unit of fluid

passing through the pipe. It is normally provided for Seametrics

sensors in pulses per gallon, and is given on the chart “K-factors

for Various Pipe Sizes.” These numbers are based on extensive

testing, which has shown close agreement between different IP

sensors in the same installation. Typically, most K-factor error

can be attributed to installation variables, such as depth setting

and fitting configuration.

It is occasionally possible to field calibrate a sensor by catching

the fluid in a measured container and comparing with the number

of pulses recorded. (To record individual pulses, set the K-factor

on the control to 1.00.) This is especially desirable if the instal-

lation has less than the recommended length of straight pipe

upstream of the sensor.


3" 4" 6" 8" 10" 12" 16" 24" 30" 36"

34.246 19.221 7.830 4.611 2.883 1.859 1.224 .577 -

-

38.329 21.844 8.779 4.980 3.213 2.097 1.304 .656 -

-

30.331 16.581 7.045 4.270 2.621 1.703 1.160 .519 .332 -

34.246 19.221 7.830 4.611 2.883 1.836

-

-

-

-

38.145 21.420 8.846 5.027 3.302 2.126

-

-

-

-

37.167 20.774 8.505 4.873 3.167 2.011

-

-

-

-

34.381 19.545 7.658 4.593 2.883 1.836

-

-

-

-

28.137 16.994 7.238 4.213 2.633 1.681 1.065 .461 .297 .207

PVC/Steel

Sch. 40

PVC/Steel

Sch. 80

Stainless Steel

(10S)

Stainless Steel

(40S)

Copper Tubing

(Type K)

Copper Tubing

(Type L)

Brass Pipe

Duct. Iron

(Class 52)

Nominal Pipe Size

Table 3: iPFs K-factors

5 to 24VDC