Chillers ultima ™ remote air cooled, Condenser specification – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual
Page 35
![background image](/manuals/370946/35/background.png)
Chillers
ULTIMA
™ REMOTE AIR COOLED
Chillers
35
Technical Manual : Part No 6259485 V1.6.0_07_2014
Condenser Specification
GENERAL SPECIFICATION
Remote Air Cooled Chiller
URAC300
URAC330
URAC360
URAC400
URAC450
Matched Condenser
– Per Unit
CE300 x 2
CE300 & CE360
CE360 x 2
CE360 & CE450
CE450 x 2
Sound Data
Sound Pressure Level at 10m
dB(A)
57
57 & 59
59
59 & 59
59 & 59
Mechanical Data
Dimensions
Horizontal - H x L x W -
mm
1383 x 6228 x 795
1383 x 6228 x 795
&
2436 x 4783 x 878
2436 x 4783 x 878
2436 x 4783 x 878
&
2436 x 4783 x 878
2436 x 4783 x 878
Vertical - H x L x W
mm
1335 x 6228 x 1272
1335 x 6228 x 1272
&
1335 x 4783 x 2436
1335 x 4783 x 2436
1335 x 4783 x 2436
&
1335 x 4783 x 2436
1335 x 4783 x 2436
Weight - Machine
kg
646
646 & 860
860
860 & 860
860 & 860
Construction - Material / Colour
Painted Galvanised Steel
– Light Grey (RAL 9002)
Condenser Coil
Nominal Airflow
m³/s
20.7
20.7 & 32.0
32.0
32.0 & 32.0
32.0 & 32.0
Discharge
Vertical or Horizontal
Fan & Motor
Quantity
4
4 & 6
6
6 & 6
6 & 6
Diameter
mm
800
800 & 800
800
800 & 800
800 & 800
Maximum Speed
rpm
890
890 & 890
890
890 & 890
890 & 890
Connections
Discharge
in
2 5/8
2 5/8 & 2 x 2 5/8
2 x 2 5/8
2 x 2 5/8 & 2 x 2 5/8 2 x 2 5/8 & 2 x 2 5/8
Liquid
in
2 1/8
2 1/8 & 2 x 2 1/8
2 x 2 1/8
2 x 2 1/8 & 2 x 2 1/8 2 x 2 1/8 & 2 x 2 1/8
Electrical Data
Nominal Run Amps
A
16.0
16.0 & 24.0
24.0
24.0 & 24.0
24.0 & 24.0
(1)
Nominal Cooling Duties based