Chillers ultima ™ remote air cooled, General specification – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual
Page 25
![background image](/manuals/370946/25/background.png)
Chillers
ULTIMA
™ REMOTE AIR COOLED
Chillers
25
Technical Manual : Part No 6259485 V1.6.0_07_2014
General Specification
ELECTRICAL DATA
URAC300
URAC330
URAC360
URAC400
URAC450
Unit Data
Nominal Run Amps
(1)
A
158
180
201
228
252
Maximum Start Amps
(2)
A
376
412
433
497
522
Permanent Supply
VAC
230V 1PH 50Hz
Mains Supply
VAC
400V 3PH 50Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
Rec Mains Fuse Size
A
200
250
250
315
315
Max Permanent Incoming Cable
Size
mm²
4 mm² terminals
Max Mains Incoming Cable Size
mm²
70 (direct to MCCB)
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
500
500
Compressor - Per Compressor
Quantity
3+3
3+3
3+3
3+3
3+3
Motor Rating
kW
14.4/14.4
17.9/14.4
17.9/17.9
22.5/17.9
22.5/22.5
Nominal Run Amps
(1)
A
25.2/25.2
32.2/25.2
32.2/32.2
40.3/32.2
40.3/40.3
Crankcase Heater Rating
W
120.0/120.0
150.0/120.0
150.0/150.0
150.0/150.0
150.0/150.0
Start Amps
(2)
225/225
272/225
272/272
320/272
320/320
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps
(1)
A
141
161
180
204
226
Maximum Start Amps
(2)
A
363
397
416
479
501
Recommended Mains Fuse
A
200
200
200
250
315
Compressor Nominal Run
Amps - Per Compressor
A
22.5/22.5
28.8/22.5
28.8/28.8
36.1/28.8
36.1/36.1
Electronic Soft-Start
Nominal Run Amps
(1)
A
158
180
201
228
252
Maximum Start Amps
(2)
A
276
303
324
369
394
Recommended Mains Fuse
A
200
250
250
315
315
(1)
Based at 12/7°C water and 45°C dew point
(2)
Starting amps refers to the direct on line connections.