Sound data, Ultima ™ remote air cooled chillers, Performance data – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual
Page 18: Chillers, Measurement of sound data, Global chiller sound level
![background image](/manuals/370946/18/background.png)
ULTIMA
™ REMOTE AIR COOLED
Chillers
18
Chillers
Technical Manual : Part No 6259485 V1.6.0_07_2014
Performance Data
SOUND DATA
Measurement of Sound
Data
All sound data quoted has been measured in the third-octave band limited values, using
a Real Time Analyser calibrated sound intensity meter in accordance with
BS EN ISO9614 Part 1 : 1995. The Global sound data quoted is valid for sound
emitted in the horizontal plane in all directions
All Sound Power Levels quoted are calculated from measured sound intensity according
to BS EN ISO9614 Part 1 : 1995.
Sound Pressure Levels are calculated from sound power using the expanded
parallelepiped method according to BS EN ISO11203 : 1996.
Global Chiller Sound Level
Standard - D Models
Sound
Measurement
Overall
dB(A)
Frequency (Hz) dB
63
125
250
500
1000
2000
4000
URAC75D
Power
84
71
50
69
81
78
79
76
Pressure
@ 10m
53
39
19
37
49
46
47
44
URAC100D
Power
83
75
48
63
79
76
77
74
Pressure
@ 10m
51
43
16
32
47
45
46
42
URAC125D
Power
85
78
53
66
78
76
81
79
Pressure
@ 10m
54
47
21
34
46
44
49
47
URAC150D
Power
85
84
55
71
80
77
81
75
Pressure
@ 10m
53
53
23
39
48
46
49
44
URAC175D
Power
87
82
54
70
78
82
83
77
Pressure
@ 10m
55
51
23
38
47
50
51
45
URAC200D
Power
88
78
53
69
75
84
84
78
Pressure
@ 10m
57
46
21
38
44
52
53
46
URAC225D
Power
92
77
55
74
81
88
88
81
Pressure
@ 10m
61
45
23
42
49
56
57
49
URAC240D
Power
90
96
90
89
90
80
82
77
Pressure
@ 10m
62
68
62
61
62
52
54
49
URAC250D
Power
94
75
56
76
83
90
90
83
Pressure
@ 10m
63
43
25
45
52
58
59
51
URAC270D
Power
91
94
89
89
89
85
84
79
Pressure
@ 10m
63
66
61
61
61
57
56
51
URAC300D
Power
91
90
88
88
86
87
85
80
Pressure
@ 10m
63
62
60
60
58
59
57
52
URAC330D
Power
95
88
90
93
91
91
90
83
Pressure
@ 10m
67
60
62
65
63
63
62
55
URAC360D
Power
98
86
91
95
94
93
92
84
Pressure
@ 10m
70
58
63
67
66
65
64
56
URAC400D
Power
98
87
92
96
95
93
92
85
Pressure
@ 10m
70
59
64
68
67
65
64
57
URAC450D
Power
99
88
93
96
95
94
93
86
Pressure
@ 10m
71
60
65
68
67
66
65
58
1
dB(A) is the overall sound level, measured on the A scale.
All performance data is supplied in accordance with BS EN 14511-1:2013
2
All sound data measured at nominal conditions: Water in/out 12/7°C at 45°C dew point.
The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If the equipment is
placed adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for each side added.