Ultima ™ remote air cooled chillers, General specification – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual
Page 22
ULTIMA
™ REMOTE AIR COOLED
Chillers
22
Chillers
Technical Manual : Part No 6259485 V1.6.0_07_2014
General Specification
MECHANICAL DATA
URAC300
URAC330
URAC360
URAC400
URAC450
Duty
– Cooling
Cooling Only
(1)
kW
331.5
373.3
415.8
459.0
502.4
Nominal Input
(1)
kW
91.3
102.8
114.4
128.7
143.1
EER
(2)
3.6
3.6
3.6
3.6
3.5
Capacity Steps
%
0-17-33-50-67-83-100 0-19-33-52-67-85-100 0-17-33-50-67-83-100 0-18-33-51-67-85-100 0-17-33-50-67-83-100
Dimensions - H x L x W
(5)
mm
1900 x 3200 x 900 1900 x 3200 x 900 1900 x 3200 x 900 1900 x 3200 x 900 1900 x 3200 x 900
Weight
Machine - D
kg
1790
1860
1940
2070
2210
- DQ
kg
1860
1930
2010
2140
2280
- DSQ
kg
1880
1950
2030
2160
2300
Operating - D
kg
1820
1900
1980
2120
2280
- DQ
kg
1900
1960
2060
2180
2340
- DSQ
kg
1900
2000
2060
2220
2360
Construction - Material / Colour
Plain Galvanised Steel Base with Galvanised Sheet Steel, Epoxy Baked Powder Paint
Superstructure
– Light Grey (RAL 7035)
Evaporator
Brazed Plate
Insulation
Class 0
Water Volume
l
30.6
35.1
39.6
46.8
55.8
Total Max. Water Flow
l/s
23.1
26.1
29.2
32.1
34.9
Compressor
Trio Scroll - Hermetic
Quantity
6
6
6
6
6
Oil Charge Volume (Total)
l
6 x 4.7
6.3+6.3+6.3+4.7
+4.7+4.7
6 x 6.3
5.9+5.9+5.9+6.3
+6.3+6.3
6 x 5.9
Oil Type
Polyol Ester
Refrigeration
Dual Circuit
Refrigerant Control
Electronic Expansion Valve
Refrigerant Type
R407C
Holding Charge
Dry Nitrogen
Connections - Evaporator
Suits
“Victaulic” type Coupling & Pipe Assembly
Water Inlet / Outlet
mm / (in)
80 (3
”)
80 (3
”)
80 (3
”)
80 (3
”)
80 (3
”)
Connections
– Condenser – CCT1
Discharge Line (Brazed)
in
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
Liquid Line (Brazed)
in
1 3/8
1 5/8
1 5/8
1 5/8
1 5/8
Connections
– Condenser – CCT2
Discharge Line (Brazed)
in
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
Liquid Line (Brazed)
in
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
Water System - Evaporator
Min. System Water Volume (3)
l
1029
1289
1286
1498
1539
Max. System Press
Bar
10
10
10
10
10
(1)
Nominal Cooling Duties based on 12/7°C water temperature and 45°C dew point, where output is the chilled water duty and
input is the compressor input power.
All performance data is supplied in accordance with BS EN 14511-1:2013
(2)
EER is the Cooling Duty
compressor input power.
(3)
For minimum system volume refer to
Minimum System Water Volume Calculations